M thermal Mono 
202004                                                                                                                                                                                                                    105 
4.25 PP Troubleshooting 
 Digital display output 
   
 
 Description 
  Water side heat exchanger inlet temperature is higher than outlet temperature in heating mode. 
  M thermal Mono stops running. 
  Error code is displayed on hydronic system main control board for refrigerant system and user interface. 
  If PP error occurs 3 times then Hb will appear. 
 
 Possible causes 
  Temperature sensor not connected properly or has malfunctioned. 
  4-way valve is blocked or damaged. 
  Hydronic system main PCB damaged.