 Procedure 
 
Water side heat exchanger water inlet / 
outlet temperature sensor is loose
1
 
Ensure the temperature sensor is 
connected properly 
Water side heat exchanger water inlet / 
outlet temperature sensor has 
short-circuited or failed
2
 
Replace the temperature sensor 
The 4-way valve is blocked or damaged
3
 
 
Notes:   
1.  Water side heat exchanger water inlet temperature sensor and water side heat exchanger water outlet temperature sensor connections are port CN6 on 
the hydronic system main PCB (labeled 8 in Figure 4-2.1 in Part 4, 2.2 “Min PCB for Hydronic System”). 
2.  Measure  sensor  resistance. If the  resistance is  too low,  the  sensor has  short-circuited.  If  the resistance  is not  consistent with the  sensor’s  resistance 
characteristics table, the sensor has failed. Refer to Part 2, 1 “Layout of Functional Components” and to Table 4-5.1 to 4-5.2 in Part 4, 5.1 “Temperature 
Sensor Resistance Characteristics”. 
3.  Restart the unit in cooling mode to change the refrigerant flow direction. If the unit does not operate normally, the 4-way valve is blocked or damaged.