4.17 P3 Troubleshooting
Digital display output
Description
Compressor current protection.
When the compressor current rises above the protection value (4/6kW models 18A, 8/10kW model 19A, 12/14/16kW
single phase model 30A, 12/14/16kW three phase model 14A), the system displays P3 protection and M thermal
Mono stops running. When the current returns to the normal range, P3 is removed and normal operation resumes.
Error code is displayed on refrigerant system main control board for refrigerant system and user interface.
Possible causes
Power supply abnormal.
Poor condenser heat exchange.
High pressure side blockage.
Inverter module damaged.
Compressor damaged.
Main PCB damaged.