and driven board in turn.
Light is off, reconnect the
power supply wire.
1.wire doesn’t connect
between main control
board PCB B and main
control board of hydraulic
module. connect thewire.
53
Error code
Malfunction or
protection
Failure cause and Correc
tiv
action
is loosen. Re connect it.
wet or there is water in.
remove the water, make
the connector dry. Add
waterproof adhesive
3. The Th sensor failure,
change a new sensor.
loosen. Re connect it.
wet or there is water in.
remove the water, make
the connector dry. Add
waterproof adhesive
3. The T2 sensor failure,
change a new sensor.
is loosen. Re connect it.
is wet or there is water in.
remove the water, make
the connector dry. Add
waterproof adhesive
3. The T2B sensor failure
,
change a new sensor.
Three times P6
protect
Same to
Communication
error between
inverter module
PCB A and main
control board PCB
B
The plate heat
exchanger
refrigerant
inlet(liquid pipe)
temperature
sensor(T2) error.
The plate heat
exchanger
refrigerant
outlet(gas pipe)
temperature senso
r
(T2B ) error.
Suction pipe sens
o
Therror
Communication
error betwee
n main
control board PCB
B and main control
board of hydraulic
module
Error code
Malfunction or
protection
Failure cause and Correctiv
action
1. The Ta senor is in the
interface;
2. The Ta sensor failure
change a new sensor or
change a new interface.
1. Strong wind or typhoon
below toward to the fan, to
make the fan running in the
opposite direction. Change
the unit direction or make
shelter to avoid typhoon
below to the fan.
2.fan motor is broken,
change a new fan motor.
1. Whether the power
supply input is in the
available range.
2. Power off and power on
for several times rapidly in
short time. Remain the unit
power off for more than 3
minutes than power on.
3. the circuit defect part of
Main control board is
defective. Replace a new
Main PCB.
1. Pressure sensor
connector is loosen,
reconnect it.
2. Pressure sensor failure.
change a new sensor.
is loosen. Reconnect it.
is wet or there is water in.
remove the water, make
the connector dry. add
waterproof adhesive
3. The T1B sensor failure,
change a new sensor.
1. The TW_out sensor
connector is loosen.
Reconnect it.
2.The TW_out sensor
connector is wet or there is
water in. remove the water,
make the connector dry.
add waterproof adhesive
3. The TW_out sensor failur
change a new sensor.
The condenser
refrigerant outlet
temperature is too
high in heating
mode for more than
10 minutes.
The outside ambient
temperature is too
high(higher than 30 , the
unit still operate heat
mode. close the heat mode
when the ambient
temperature is higher than
30
Pressure sensor
failure
The system outlet
water temperature
sensor T1B failure.
The plate heat
exchanger water
outlet temperature
sensor (TW_out)
error.
The indoor
temperature
sensor(Ta) error
The DC fan failure
Main circuit voltage
failure
2.Communication wire
sequence is not right.
Reconnect the wire in the
right sequence.
3. Whether there is a high
magnetic field or high
power interfere, such as
lifts, large power
transformers, etc..
To add a barrier to protect
the unit or to move the un
it
to the other place.
2.if light is on, check the
wire connection between
the main PCB and driven
or change a new wire.