M thermal Mono 
202004                                                                                                                                                                                                                    67 
 
 
 Description 
  Communication error between refrigerant system main control chip and the inverter driver chip. 
  M thermal Mono stops running. 
  Error code H1 is displayed on refrigerant system main control board and user interface. 
 
 Possible causes 
  Power supply abnormal. 
  Transformer malfunction. 
  Interference from a source of electromagnetic radiation. 
  Refrigerant system main PCB or inverter driven module damaged. 
 
 Procedure 
 
Power supply for refrigerant system main 
control board for refrigerant system and 
transformer is abnormal
1
 
Provide normal power supply 
The transformer has malfunctioned
2
 
There is a source of electromagnetic 
radiation near the unit, such as 
high-frequency transmitter or other high 
strength radiation device 
Remove the source of interference 
Replace outdoor refrigerant system main 
control board for refrigerant system and 
inverter driven module in turn 
 
Notes:   
1.  Measure the voltages of transformer input port and on the main PCB. The normal voltage between transformer input port terminals is 220V, output two 
sets  of  voltages  11V  and  17V.  If  one  or  more  of  the  voltages  are  not  normal,  the  power  supply  for  main  control  board  for  refrigerant  system  and 
transformer is abnormal. 
2.  Measure the voltages of transformer output ports. If the voltages are not normal, the transformer has malfunctioned.