4.12 H6, HH Troubleshooting 
 Digital display output 
   
 
 Description 
  H6 indicates a DC fan error.   
  HH indicates that H6 protection has occurred 10 times in 2 hours. When an HH error occurs, a manual system restart 
is required before the system can resume operation. The cause of an HH error should be addressed promptly in order 
to avoid system damage. 
  M thermal Mono stops running. 
  Error code is displayed on refrigerant system main control board for refrigerant system and user interface. 
 
 Possible causes 
  Power or communication wires not connected properly. 
  High wind speed. 
  Fan motor blocked or has failed. 
  Power supply abnormal. 
  PFC module damaged. 
  IPM module damaged. 
  Main PCB damaged.