EasyManuals Logo

Midea MHC-V4W/D2N8-B User Manual

Midea MHC-V4W/D2N8-B
113 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #98 background imageLoading...
Page #98 background image
M thermal Mono
96 200204
Midea M thermal Mono Service Manual
Condition 4: L0 error appears after the compressor has been running for a period of time and the compressor speed is
over 60rps
L0
Inverter module has overheated
Yes
Repaint the thermally conductive silica
gel on the PFC and IPM modules (on the
reverse side of the inverter module PCB)
1
No
Inverter module is over-current
2
Yes
Replace the compressor
No
Replace the inverter module
2
Notes:
1. When replacing an inverter module, a layer of thermally conductive silica gel should be painted on the IPM module (on the reverse side of the inverter
module PCB).
2. Use clip-on ammeter to measure the compressor current, if the current is normal indicates the inverter module is failed, if the current is abnormal
indicates the compressor has failed.
Situation 5: L0 error appears occasionally/irregularly
L0
The outdoor unit ventilation is not good
Yes
Ensure enough space for unit ventilation
Midea CAC Confidential

Other manuals for Midea MHC-V4W/D2N8-B

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Midea MHC-V4W/D2N8-B and is the answer not in the manual?

Midea MHC-V4W/D2N8-B Specifications

General IconGeneral
BrandMidea
ModelMHC-V4W/D2N8-B
CategoryAir Conditioner
LanguageEnglish

Related product manuals