Electrical Control Function
Electrical Control 109
18
16
Low
High
1.3.3.2 Indoor fan running rules:
When the compressor is on, the indoor fan can be set to high/med/low/auto. And the anti-cold wind function
has the priority.
For Ceiling & Floor: If the compressor stops caused by the room temperature rising, the indoor fan will follow
the below rules. During this period, the anti-cold-wind is disabled.
Auto fan action:
For CEILING & FLOOR: floor installation:
T1-TS
0C Medium Low
-1C
-2C
High
T2
TE14+2
TE14
Setting
Low for15s, then
off