1 T1 ≥ TS+2
Low
Breeze
ON 6 minutes
OFF 4 minutes
2
TS ≤T1<TS+2
Low
Breeze
ON 5 minutes
OFF 5 minutes
3
T1 < TS
Low
Breeze
ON 4 minutes
OFF 6 minutes
8.4.5.2 In drying mode, if room temperature is lower than 10 ℃, the indoor fan will run at breeze while
the compressor and outdoor fan will stop and not resume until room temperature exceeds 13 ℃.
8.4.5.3 For MS9A-18CR-PC4W(A) model, MS9A-18CR-QB8, MS9A-18CR-QC0(A) ,
MS9A-18CR-QC2 ,MS9A-18CR-QC4(A), MS9A-21HR-QB6W,MS9A-22CR-QB8 ,
MS9A-22CR-QC0 , MA9A-24HR-QB4W models, the indoor fan speed will keep at low speed and all
the protection is the same as the cooling mode.
8.4.5.4 For MS9A-09CR-QC4(A), MS9A-12CR-QC4(A), MS9A-18CR-QC0 models, the compressor is
cycled running with 10 minutes on and then 5 minutes off. The indoor fan will keep running at low
speed.
8.4.5.5 The system protection is active in this mode.
8.4.6 Forced operation function
Press the touch button continually, the AC will run as below sequence:
Forced auto →Forced cooling →Off
Forced cooling mode:
The compressor and outdoor fan keep running and the indoor fan runs at low speed. After running for
30 minutes, AC will turn to drying mode(auto mode for MS9A-09CR-QC4(A), MS9A-12CR-QC4(A),
MS9A-18CR-PC4W(A), MS9A-18CR-QB8, MS9A-18CR-QC0, MS9A-18CR-QC0(A),
MS9A-18CR-QC2, MS9A-18CR-QC4(A), MS9A-21HR-QB6W, MS9A-22CR-QB8, MS9A-22CR-QC0 ,
MA9A-24HR-QB4W models) with 24℃ setting temperature.