6. Installation details
6.1 Wrench torque sheet for installation
Outside diameter Torque Additional tightening torque
·
·
Ф6.35 1/4
1500
(153kgf.cm)
1600
(163kgf.cm)
Ф9.53 3/8
2500
(255kgf.cm)
2600
(265kgf.cm)
Ф12.7 1/2
3500
(357kgf.cm)
3600
(367kgf.cm)
Ф16 5/8
4500
(459kgf.cm)
4700
(479kgf.cm)
6.2 Connecting the cables
The power cord of connect should be selected according to the following specifications sheet.
Grade
Unit
18K 24K
mm
2
2.5 2.5
6.3 Pipe length and the elevation
Capacity
Btu/h
Pipe size Standard
length
(m)
Max.
Elevation
B (m)
Max.
Length
A (m)
Additional
refrigerant
(g/m)
Gas Liquid
18K 1/2’’(Ф12.7) 1/4"(Ф6.4) 5 10 25 20
24K 5/8’’(Ф16) 3/8’’(Ф9.53) 5 10 25 40