Service manual 
39 
 
The set temperature rise 1℃ per hour. Two hours later, the set temperature will maintain as a constant and 
the fan speed is kept at low speed. 
The total time is 7 hours, after 7 hours the unit stops. 
11.11.3 Heating: 
The set temperature decrease 1℃ per hour. Two hours later, the set temperature will maintain as a 
constant and the air circulation is kept at low speed (Anti-cold function takes precedence over all). 
The total time is 7 hours, after 7 hours the unit stops. 
11.11.4 Auto: 
After an hour running under economic mode, the set temp will rise 1℃,if it is under cooling mode; the set 
temp will decrease 1℃,if it is under heating mode; the set temp will be changeless, if it is under fan-only 
mode; the condition will be the same after the air conditioner running under economic mode after 2 hours, 
and during the next time the set temp do not change. The total time is 7 hours, after 7 hours the unit stops. 
 
11.12  Auto restart function 
In case of a sudden power failure, this function automatically sets the unit to previous settings before the 
power failure when power returns. 
 
 
11.13  Turbo mode 
In cooling mode, when pressing the turbo button on the remote controller, the unit will enter turbo mode with 
ultra-high speed and reach the set temperature more quickly. After running 20 minutes in turbo mode, the 
indoor fan will automatically recover the preset speed. 
 
11.14  PLASMA ( optional) 
Starts with indoor fan. 
Note: Plasma and Anion can be use together. 
 
11.15  Anion( optional) 
Starts with indoor fan. 
Note: Plasma and Anion can be use together.