Midea Tropical R410A High Efficient Duct Technical Manual 50Hz MCAC-UTSM-201707
89
general, it is not allowed to parallel connection two wires, unless welding joint is well welded and
wrapped with insulating tape.
Every pole of the all-pole disconnection device should have at least 3mm separation distance
and a leakage protector with the rating current above 10mA shall be installed together when
wiring.
All electrical wiring is finished, power on as long as it is confirmed that all wires are connected
correctly and fixed tightly.
Notes:
For outdoor units, remove the screws at the side of the corner panel, and slide corner panel down
and remove from unit.
6.2 Specifications of power supply
Indoor units: