EasyManuals Logo

Midea MTA-76CRN1 Service Manual

Midea MTA-76CRN1
105 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #44 background imageLoading...
Page #44 background image
DM13-01.01.16en Air-cooled Package
Service manual 43
Operation lamp flashes:
Defrosting lamp flashing at 5Hz
Condenser temperature sensor malfunction
Judge 1: Check condenser temperature sensor is break off.
Replace temperature sensor
Yes
Judge 2: Condenser temperature sensor is abnormal.
No
Validate: Check whether the resistance of the condenser
temperature sensor is correct according to Annex 1.
Replace temperature sensor
No
Yes
Replace indoor PCB.

Other manuals for Midea MTA-76CRN1

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Midea MTA-76CRN1 and is the answer not in the manual?

Midea MTA-76CRN1 Specifications

General IconGeneral
BrandMidea
ModelMTA-76CRN1
CategoryAir Conditioner
LanguageEnglish

Related product manuals