2.3  Fan Mode
When fan mode is activated:
• The outdoor fan and compressor cease operation.
• Temperature control is disabled and no temperature 
setting is displayed.
• The indoor fan speed can be set to high, medium, low, 
or auto.
• The louver operations are identical to those in cooling 
mode.
2.4  Cooling Mode
2.4.1  Indoor Fan Control
• In cooling mode, the indoor fan operates continuously. 
The fan speed can be set to high, medium, low or auto.
• The auto fan acts according to the value of T1-TS.
2.4.2  Outdoor Fan Control
• The outdoor fan is controlled by T4.
2.4.3  Evaporator Temperature Protection
When T2<4°C for 250 seconds or T2<0°C, the compressor 
and outdoor fan cease operation and resume to normal 
when T2>8°C and the time of protection is no less than 3 
minutes.
2.4.4 Condenser Temperature Protection
When condenser temperature is more than setting value, 
the compressor ceases operations.
2.5  Heating Mode(Heat pump models)
2.5.1  Indoor Fan Control
• When the compressor is on, the fan speed can be set 
to high, medium, low, or auto. And the anti-cold wind 
function has the priority.
• The auto fan acts according to the value of T1-Ts.
2.5.2  Outdoor Fan Control
• The outdoor fan is controlled by T4.
2.5.3  Defrosting mode 
• The unit enters defrosting mode according to the 
value of temperature of T3 and the value range of 
temperature change of T3 and also the compressor 
running time.
• If any one of the following items is satisfied, the 
defrosting will finish and the machine will turn to 
normal heating mode.
• T3 rises to be higher than TCDE1°C.
• T3 keeps to be higher than TCDE2°C for 80 
seconds.
• The machine has run for 10 minutes in defrosting 
mode.
2.5.4  Evaporator Temperature Protection
When the evaporator temperature exceeds a preset 
protection value, the compressor and outdoor fan cease 
operations, the outdoor fan motor ceases operation 30 
seconds later.
2.5.5  Prevent Over-Heating
In heating mode, when the indoor unit has no capacity 
requirement due to indoor room temperature increased, 
the Indoor fan will run in super breeze. (Anti-cold wind 
function has the priority)
2.6  Auto Mode
• This mode can be selected with the remote controller 
and the temperature setting can be adjusted between 
17°C~30°C
• In auto mode, the machine selects cooling, heating, or 
fan-only mode on the basis of △T (△T =T1-Ts).
∆T Running mode
∆T>2°C Cooling
-2°C≤∆T≤2°C Fan-only
∆T<-2°C Heating*
Heating*: In auto mode, cooling only models run the fan.
• Indoor fans run at the auto fan speed of the relevant 
mode.
• The louver operates the same as in relevant mode.
• If the machine switches mode between heating and 
cooling, the compressor pauses for a certain period of 
time intermittently and then selects a mode based on 
T1-Ts.
• If the setting temperature is modified, the machine 
selects a new running function.
2.7  Drying Mode
• Indoor fan speed is fixed at low and cannot  be 
changed. 
•  Low indoor room temperature protection
• In drying mode, if room temperature is lower than 
10°C, the indoor fan will stop and not resume until 
room temperature exceeds 12°C.
• All protections are activated and operate the same as 
they do in cooling mode.
•  The louver operates the same as in cooling mode.