Midea V6-i Series Service Manual
 
5.2 Compressor Output Control 
The compressor rotation speed is controlled according to the load requirement. Before compressor startup, the outdoor 
unit first estimates the indoor unit load requirement according to the nominal capacity of indoor units currently running, 
and then correct for ambient temperature. The compressors then start up according to the corrected load requirement.   
 
During operation the compressors are controlled according to the nominal capacity of indoor units currently running and 
the indoor unit heat exchanger temperatures. 
 
5.3 Compressor Step Control 
The running speed of the compressors in rotations per second (rps) is one third of the frequency (in Hz) of the electrical 
input to the compressor motors. The compressor speed can be altered in increments of 1 rps. 
 
5.4 Operating Priority and Rotation of Compressors 
Figures 3-5.1 shows the compressor operating priority and rotation in the  outdoor unit. In units with  two compressors, 
inverter compressor A (BP1) operates in priority to inverter compressor B (BP2).   
 
Figure 3-5.1: Compressor priority and rotation – one outdoor unit