2.  The DC bus wire should run from the N_in terminal on the inverter module, through the current sensor (in the direction indicated by the 
L0 protection
The DC bus wire connected incorrectly
1
Ensure the wire is 
connected properly
The compressor wiring is connected 
incorrectly
Reconnect the cables 
based on wiring diagram
Replace the compressor
The inverter module is not well heat 
dissipation
The IPM screws is loosen
Fasten IPM 
screws again
The silica gel is coated not 
well for heat radiation
Coat with silica 
gel
The compressor has less than 12 hours 
preheating before initial operating
Switch on power again to detect 
whether the compressor can start
Refer to “P3 over current protection”
Replace the inverter 
module
Ensure enough 
preheating time
No
No
No
No
No
No
Yes
Yes
Yes
Yes
Yes
Yes
Yes
No
Yes
Yes
No
No
Disconnect
the power
supply
The resistance between 3 phases of 
compressor is over 5Ω
The insulation resistance of 
compressor is less than 100kΩ