VC Pro VRF 50/60Hz 
    177 
Part 3 - System Design and Installation 
6.6 Watertightness Test and Water Flow Test 
Once installation of a drainage piping system is compete, watertightness and water flow tests should be performed. 
 
 
7 Insulation 
7.1 Refrigerant Piping Insulation 
7.1.1 Purpose   
During operation, the temperature of the refrigerant piping varies. Insulation is required to ensure unit performance and 
compressor lifespan. During cooling, the gas pipe temperature can be very low. Insulation prevents condensation forming 
on the piping.   
 
7.1.2 Selecting insulation materials 
Use heat-resistant polyethylene foam for the liquid pipes (able to withstand temperature of 70°C), and polyethylene foam 
for the gas pipes (able to withstand temperature of 120°C). Reinforce the insulation layer of the refrigerant piping based on 
the installation environment.   
 
7.1.3 Thickness of insulation 
Minimum thicknesses for refrigerant piping insulation are specified in Table 3-7.1. In hot, humid environments, the thickness 
of insulation should be increased over and above the specifications in Table 3-7.1.   
Table 3-7.1: Refrigerant piping insulation thickness 
Minimum insulation thickness (mm) 
Humidity < 80%RH 
Minimum insulation thickness (mm) 
Humidity ≥ 80%RH 
 
   
Watertightness test 
  Fill the piping with water and test for leakages over a 24-hour period. 
 
Water flow test (natural drainage test) 
  Slowly fill the drainage pan of each indoor unit with at least 600ml of water through the inspection port and check 
that the water is discharged through the outlet of the drain piping. 
 
Caution 
  The  drain  plug  in  the  drainage  pan  is  for  removing  accumulated  water  prior  to  performing  indoor  unit 
maintenance. During normal operation, the drain should be plugged to prevent leakage.