Part 1 - General Information 
4.2 Heat recovery ventilator 
AC Series 
 
 
DC Series 
 
Series category (D: DC series) 
4.3 Outdoor Units 
 
VC Pro series outdoor units 
Capacity index (the capacity in kW multiplied by 10) 
Unit category (W: VRF outdoor unit) 
Type (V2: All DC inverter) 
Power supply (G: 3 phase, 380-415V, 50/60Hz) 
Refrigerant type (N1: R410A) 
 
5 Combination Ratio 
 
 
Table 1-5.1: Indoor and outdoor unit combination ratio limitations 
Minimum 
combination ratio 
Maximum combination ratio 
Standard indoor 
units only 
Fresh air processing 
units only 
Fresh air processing units and 
standard indoor units together 
VC Pro series outdoor units 
Notes:   
1.  The total capacity of the indoor units can be up to a maximum of 130% of the combined capacity of the outdoor unit for a system where not all the indoor 
units are operating at the same time. 
2.  When fresh air processing units are installed together with standard indoor units, the total capacity of the fresh air processing units must not exceed 30% 
of the total capacity of the outdoor units and the combination ratio must not exceed 100%. 
 
 
Sum of capacity indexes of the indoor units 
Capacity index of the outdoor units