Use  U-shaped  branch  joints  as  specified  on  the 
construction drawings  –  do not  replace  U-shaped  branch 
joints with tee joints. 
  To avoid accumulation of oil in the outdoor units, outdoor 
branch joints should be installed horizontally and must not 
be higher than the outdoor unit refrigerant outlets. Refer 
to Figure 3-5.9. 
  Indoor branch joints may be installed either horizontally or 
vertically. Horizontal branch joints must be installed at an 
angle to the horizontal not exceeding 10° in order to avoid 
uneven  distribution  of  refrigerant  and  possible 
malfunction. Refer to Figure 3-5.8. 
 
  To ensure even distribution of refrigerant, a limitation is placed on how close branch joints may be installed to 
bends, other branch joints and the straight sections of piping leading to indoor units. Refer to Part 3, 4.6 “Branch 
Joints”.