18
Test capacitor.
Replace if not within +/-10% of manufacture's rating.
Check bearings. Replace the motor if the blower wheel cannot
rotate freely.
Pay attention to any change from high speed to low speed.
Replace the motor if the speed does not change.
Compressor stops
instantly after
startup.
The amount of the refrigerant is too much, making the
compressor load too big. Recycle and recharge the refrigerant
after checking for the reason.
The compressor is blocked inside. Replace after checking for
the reason.
Check voltage at electrical outlet. Correct if none.
Check and correct if water alarm happens.
Check voltage at the power cord terminal on Main PCB.
Replace the power cord if none.
Transformer (Discharge
transformer before testing)
Check resistance between the two input/output lines on
transformer. Replace the transformer if either of the
input/output is open or the transformer is damaged.
Wire disconnected or
connection loose
Connect wire. Refer to wiring diagram for terminal
identification. Repair or replace loose terminal.
Select fan speed and Check the voltage on main PCB. Replace
the main PCB if no voltage in anyone.
Capacitor (Discharge
capacitor before testing)
Test capacitor.
Replace if not within +/-10% of manufacture's rating. Replace if
shorted, open or damaged.
Fan blower hitting scroll. Realign assembly.
Check fan motor bearings. Replace the motor if motor shaft do
not rotate.
Replace the fan blower if cracked, out of balance, or partially
missing.
Replace the motor if knocking sounds continue when running
or loose, or the motor hums or noise appears to be internal
while running.
Compressor will
not run while fan
motor runs.
Check voltage. Call Supply Authority if not within limits.
Check the wire connections, if loose, repair or replace the
terminal. If wires are off, refer to wiring diagram for
identification, and replace. Check wire locations. If not per
wiring diagram, correct.
Check voltage of main PCB. Replace the main PCB if open.
Capacitor (Discharge
capacitor before testing)
Check the capacitor.
Replace if not within +/-10% of manufacturers rating. Replace
if shorted, open, or damaged.
Check the temperature setting if not at the coolest (in cooling
mode) or the warmest (in heating mode). Set it if not.
Check the compressor for open circuit or ground. If open or
grounded, replace the compressor.
Remove the cabinet and carefully rearrange tubing not to
contact cabinet, compressor, shroud and barrier.
Water depth is over load in
chassis(P1)
Use a drain hose and a pan to drain the condensed water in the
chassis.
Water depth sensor if
failure
Check and replace if failure.
shaded pole motor failure
Check and replace if the motor is failure.
Cooling or heating
feels not good
Clean or replace if restricted.
Realign and assemble if the installation of the air discharging
pipe failure. Replace if damaged.