High Temperature Hydro Module
76 202003
Midea
VR High Temperature Hydro Module
13.9.5 Setting of Special Functions
Maximum Power Limitation Function
This function can limit the power consumption of the hydraulic module. Choose MENU > FOR SERVICEMAN > POWER INPUT
LIMITATION. Press OK. The following interface is displayed.
Select speed. 0 = Not limited; 1 = Speed 1; 2 = Speed 2; 3 = Speed 3.
Speed 0: It indicates that the maximum current for hydraulic module operation is 16 A.
Speed 1: It indicates that the maximum current for hydraulic module operation is 15 A.
Speed 2: It indicates that the maximum current for hydraulic module operation is 14 A.
Speed 3: It indicates that the maximum current for hydraulic module operation is 13 A.
Heat recovery Function
This function will automatically enable the heat recovery function of the hydraulic module to produce hot water when the
start-up capacity of the chillers IDU is great. Choose MENU > FOR SERVICEMAN > HEAT RECOVERY MODE SETTING. Press OK.
The following interface is displayed.
HEAT RECOVERY=YES indicates that the heat recovery function is enabled. HEAT RECOVERY=NON indicates that heat
recovery function is disabled.
Ttank_recovery_max indicates that the desired tank temperature of the heat recovery function is set.