V8 VRF Indoor Units
24
Midea
V8
Series VRF Indoor Units
Table 2.2: Indoor unit Parameter Settings(continues)
Paramet
er
Code
Parameter Name
Parameter
Range
Default
Value
Remarks
N64
Valve enabled/ disabled
at the time of heating
Selection of auxiliary
heater
00/01
00
00: Valve enabled at the time of heating
01: Valve disabled at the time of heating
Note: Applicable to fan coil unit only
N65
Set anti hot air
temperature for IDU
cooling [anti hot air
temperature of fan coil
unit of the old platform]
00/01/02/03/04
00
Fan coil unit: 00: 0°C
01: -2°C
02: -4°C
03: -6°C
04: Anti hot air invalid (water inlet temperature - indoor
ambient temperature)
N66
Auto Dry
00/01
00
00: Invalid(default)
01: Valid
Note: Applicable to cooling operation in cooling mode or
auto mode
N67
Target relative humidity
of Auto Dry
00/01/02/03/04
/05/06
02
00: 40%,
01: 45%,
02: 50% (default),
03: 55%,
04: 60%,
05: 65%,
06: 70%
Notes:
If use other controllers, parameter settings need refer to the corresponding manual.