V8 VRF Indoor Units
31
Troubleshooting Guide
4.4 Fan Control
4.4.1 Fan speeds control
The IDU can work in seven-speeds
Seven-speeds
When the Indoor Unit detects only seven wind speeds the wind speed is set as follows.
Sleep Speed 1 Speed 2 Speed 3 Speed 4 Speed 5 Speed 6 Speed 7 Auto
For the specific model type, please consult the technical manual of each model. The following table describes the fan
control in different situations
Fan control in different situations
Operating
in Set
Speed
IDU Status
Cooling Mode
Dry Mode
Heating Mode
Fan Mode
Speed Switch
Operating
Set speed
Speed 1
Set speed
Set speed
User set
Standby
Set speed
Speed 1
Termal
/
Off
Stop fan
Stop fan
Stop fan
Stop fan
Fault
Stop fan
Stop fan
Stop fan
Stop fan
Automatic
Fan Speed
IDU Status
Cooling Mode
Heating Mode
Auto
Fan Mode
Speed Switch
Operating
Automatic
Automatic
Automatic
Low
Switch fan speed
based on the
difference of the set
temperature and
return air
temperature
Standby
Automatic
Termal
Automatic cooling, automatic fan speed,
automatic heating, and Termal mode
operating
/
Off
Stop fan
Stop fan
Stop fan
Stop fan
Fault
Stop fan
Stop fan
Stop fan
Stop fan
Note:
Termal: In the heating mode, The IDU in the standby state heating mode will run fan periodically at speed 1 for one minute (the period can be set)
4.4.2 Auto fan control mode
1. When set auto fan control in cooling or heating mode. After operation in the initial speed for a period of time, when
Thermal ON, IDUs enter the auto mode and the fan speed will be changed every 2 minutes or when Ts change.
2. When Thermal OFF, IDUs enter the standby mode. When Thermal ON, IDUs enters the initial fan speed again.
3. The default speed is speed 1 when IDUs are set auto fan mode in Air supply only mode.
Determine the initial fan speed of auto fan control
The initial fan speed is determined according to the difference
between ambient indoor temperature (T1) and set temperature (TS),
and it updates in the following situations:
1) The first time enter this mode
2) TS is changed
3) When switching between normal operation and silent operation