6.1.6 A73 - The error of the linked FAPU is transmitted to the master IDU (non-series connection)
Note:
1) The type of FAPU may be HRV, VRF fresh air IDU and so on.
2) Series setting: The linked FAPU and the master IDU are connected to the air supply duct and air return duct respectively and
separately. A wired controller is used to set this installation method as a non-series connection.
Display position (master IDU)
Spot check interface
query
Error code is not
displayed
Master IDU: operates normally. FAPU: stops. Other IDUs of the same system: operate normally.
ODU of the same system: operate normally.
The error of the linked FAPU is transmitted to the master IDU
The FAPU is faulty.
The master IDU's main control board is damaged.
A71/A73
Error in FAPU
After troubleshooting, is the
master IDU error
code cleared?
Replace the the main control
board of the master IDU
Fault cleared
Yes
No
Obtain the linked error code (1)
of the FAPU, and refer to the
corresponding error handling
method in the maintenance
manual of the FAPU for
troubleshooting
Note:
1. The error code can be queried after the FAPU is connected to the wired controller or the display
box.