6.1.18 C51 - Abnormal communication between the IDU and wired controller
Note: The error code C51 can be triggered either at the IDU side or at the wired controller side.
Triggered at the IDU side
Triggered at the wired
controller side
The error code "C51" can be
queried by entering the spot
check interface of the panel or
display box, but the error code is
not displayed on the wired
controller.
The error code "C51" is
displayed only on the wired
controller rather than on the
panel or display box.
Triggered at the IDU side: The faulty IDU and other IDUs of the same system: operate normally.
Triggered at the wired controller side: The wired controller is unavailable.
ODU of the same system: operate normally.
Triggered at the IDU side: If the main control board of an IDU has lost communication with wired
controller for 2 min
Triggered at the wired controller side: If the wired controller has not received any reply from the main
control board of an IDU for 1 min
The wired controller is damaged
The IDU main control board is damaged.
Communication cables are loose or the communication port is faulty.
Communication cables have short-circuited or been cut off.
C51
Are communication cables
loose or communication ports
wrong?
Properly connect the cables
and ensure they are connected
to the right ports
Replace the main control
board of the IDU
No
Yes
Is the fault cleared after
replacing the wired controller?
The wired controller is
damaged, so change the wired
controller
Yes
No
Is the communication
cable disconnected or short
circuited?
Replace the communication
cable and properly connect the
cable
Yes
No