V8 VRF Indoor Units
75
Troubleshooting Guide
6.1.28 d16 - Air inlet temperature of IDU is too low in heating mode
Error display
Digital display
Display position
Panel, display box, and wired controller
Error impact
The faulty IDU stops. Other IDUs of the same system: operate normally.
ODU of the same system: operate normally.
Error trigger
If the air inlet temperature of the IDU is lower than the set value (See the operating temperature
range set out in the IDU Manual) for 5 min in heating mode
Error recovery
Automatic recovery
Possible cause
See the Troubleshooting section.
Troubleshooting
d16
Cause 4: If the error cannot be
cleared after causes 1/2/3 have
been eliminated, the main control
board of the IDU is damaged
Cause 3: The sensor body
comes into contact with a cold
source, such as low-temperature
condensed water and cold
surface of a heat exchanger,
which causes the detected value
to be lower than the normal value
Cause 2: Remove the plug of the
inlet air temperature sensor from
the main control board of the
IDU, measure its resistance
value, and compare it with the
Table of Sensor Resistance -
Temperature Characteristics (1).
If the temperature that
corresponds to the resistance
value deviates from the actual
inlet air temperature by more
than 5°C , the sensor is
damaged.
Replace the inlet air
temperature sensor
Replace the main control
board of the IDU
Eliminate the interference
of external cold source to
the sensor
Cause 1: Spot check the inlet air
temperature and measure the
inlet air temperature. If the point
check result is the same as the
measured result (error 1°C ), it
is a normal protection measure
for the unit. Otherwise, refer to
cause 2/3/4
It is a normal protection
measure for the IDU.
When the inlet air
temperature exceeds the
set value, the fault will be
cleared
Note:
1. The inlet air temperature sensor is commonly found in the fresh air IDUs (The sensor code is
defined as T0), and its resistance and temperature characteristics are similar to T1 - return air
temperature sensor. Please refer to the Table of Temperature Sensor Resistance Characteristics
listed in the Maintenance Manual to learn more about the sensor's features.