EasyManua.ls Logo

Midea V8 VRF Series - Page 79

Midea V8 VRF Series
109 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
V8 VRF Indoor Units
78
Midea
V8
Series VRF Indoor Units
6.1.31 dE2 - PM2.5 sensor fault
Error display
Digital display
Display position
Panel, display box, and wired controller
Error impact
The faulty IDU and other IDUs of the same system: operate normally.
ODU of the same system: operate normally.
Error trigger
If the main control board of an IDU has lost communication with PM2.5 sensor for 2 min
Error recovery
Automatic recovery
Possible cause
See the Troubleshooting section.
Troubleshooting
dE2
Cause 3: The IDU main control board
is damaged
Cause 4: If the error cannot be cleared
after causes 1/2/3 have been
eliminated, the PM2.5 sensor is
damaged
Replace the main
control board of the
IDU
Replace the PM2.5
sensor (1)
Cause 1: The communication cable
between the PM2.5 sensor and the
sensor control board becomes
disconnected or short circuited
Replace the
communication
cable and properly
connect the cable
Cause 2: The communication cable
between the PM2.5 sensor and the
adapter board has become loose
Connect the cable
properly
Note:
1. If the PM2.5 sensor is integrated with the sensor control board, making disassembly difficult, then replace
the sensor control board directly.

Related product manuals