press display will show
0.0 0 0
F - 2
(then)
- - - -
2.1 5 6
F - 3
(then)
- - - -
6.0 0 5
F - 10
(then)
- - - -
5 1.1 2
F - 11
(then)
- - - -
5 8.8 3
F - 11
P - 4 0
P-41 enter option "1", flowrate time units per sec
P-46 enter "58.83", maximum flowrate in cu ft / sec
P-49 enter option "3", flowrate decimal point display max
3 digits after decimal
P-52 enter option "0", totalizer convert display is divided by 1 before
being displayed or 1 count per thousand cu ft
P-53 enter option "2", totalizer decimal point display 2 digits after
decimal or resolution equals 1/100th of a count
to re-enter run mode
» » »
5
5
ENTER
6
1
50
6
ENTER
2
2
ENTER
1
0
1
0
ENTER
8
3
CLR
5 8
ENTER
ALT
DISP
RUN
CAL
PL-443 6 – 41