Command Mode - Configuration & Operation
14
Alert sounds for monitor input activation. Default is disabled.
Panel Configuration/Features/Device LED flashing
This feature allows flashing of the LED on the addressable sensors to flash momentarily, while polling, if enabled.
The input and output modules LED always flashes, while polling, regardless of this feature enabled or disabled.
Panel Configuration/Features/Class-A loop
This feature configured the addressable loop as Class-A if enabled.
Panel Configuration/Features/Auto after hours
This feature allows the daytime/nighttime mode to be set automatically if enabled.
Panel Configuration/Features/Two stage operation
If this feature is enabled the system is configured as two-stage system, if not enabled, it is a single stage system.
Use this function to allow the system to perform a two-stage operation if enabled. This selection also sets the Auto
General Timer to 5 minutes. If the Auto Signal Silence Timer is greater than the Auto General Alarm Timer, then no
error will occur. If the Auto Signal Silence Timer is equal or less than the Auto General Alarm Timer, then the Auto
Signal Silence Timer is disabled and the following warning message is displayed: “Auto Sig. Sil. Has been disabled”
The user should set the Auto Signal Silence Timer is always greater than the Auto General Alarm Timer.
Panel Configuration/Features/General alarm timer
This feature sets the value for the general alarm timer
Panel Configuration/Features/Common alarm relay operation
This feature sets the operation of the common alarm for two stage system.
3RROHGGHY IODVKHV
>@ (QDEOHG
/RRSFODVV$
>@ (QDEOHG
$XWRDIWHUKRXUV
>@ (QDEOHG
7ZRVWDJHRSHUDWLRQ
>@ (QDEOHG
Auto gen .alarm timer
[X] Disabled
[ ] 5 min
[ ] 10 min
[ ] 15 min
[ ] 20 min
[ ] 30 min
Common alm rly . oper
[ ] Both stages
[X] Second stage