What to do if my Mitsubishi Electric Inverter shows overcurrent trip during acceleration?
- BBrian SheaAug 23, 2025
If your Mitsubishi Electric Inverter is showing an overcurrent trip during acceleration, try the following: Set a longer acceleration time. If 'E.OC1' appears at start, disconnect the motor and restart the inverter. If the error persists, the inverter may be faulty, so contact your sales representative. Check the wiring for output short circuit and ground fault. If the rated motor frequency is 50Hz, set Pr. 3 Base frequency to 50Hz. Lower the stall prevention operation level. Activate the stall prevention operation and the fast-response current limit operation (Pr.156). If operating with frequent regenerative driving, set the base voltage in Pr. 19 Base frequency voltage.