4 SAFETY FB SPECIFICATIONS
4.11 M+SF_MUTEP_R
8112H Muting Backward Active 2 Muting backward sequence is still active. Both exit switches
i_bMutingSw_11 and i_bMutingSw_12 are actuated and the
monitoring of i_dDiscTime11_12 is stopped.
o_bReady: ON
o_bS_AOPD_Out: ON
o_bS_MutingActive: ON
o_bError: OFF
Complete muting within
i_dMaxMutingTime.
Please do the above actions when the FB detects an error or is in an unexpected state. However, when the situation is still not corrected, please check the
following.
A failure in safety devices and emergency stop devices
Wiring and status of a safety remote I/O module and a safety programmable controller
Programming logic, the memory allocation of safety devices, and the connections of safety FB variables
Setting of i_bS_StartReset
o_wDiagCode
(Hexadecimal)
State name Description, output setting Action
WARNING