4 SAFETY FB SPECIFICATIONS
4.11 M+SF_MUTEP_R
77
4
8012H Muting Forward Active 1 Muting forward sequence is active when both i_bMutingSw_11
and i_bMutingSw_12 have been actuated in the same cycle or in
serial.
Monitoring of i_dDiscTime11_12 is stopped. Monitoring of
i_dMaxMutingTime is activated, when transition came directly from
state 8000H.
o_bReady: ON
o_bS_AOPD_Out: ON
o_bS_MutingActive: ON
o_bError: OFF
Complete muting within
i_dMaxMutingTime.
8014H Muting Forward Step 1 Muting forward sequence is active. i_bMutingSw_21 is the first exit
switch actuated. Monitoring of i_dDiscTime21_22 is started.
o_bReady: ON
o_bS_AOPD_Out: ON
o_bS_MutingActive: ON
o_bError: OFF
Set both muting switches
(i_bMutingSw_21 and
i_bMutingSw_22) to ON.
Complete muting within
i_dMaxMutingTime.
8314H Muting Forward Step 2 Muting forward sequence is active. i_bMutingSw_22 is the first exit
switch actuated. Monitoring of i_dDiscTime21_22 is started.
o_bReady: ON
o_bS_AOPD_Out: ON
o_bS_MutingActive: ON
o_bError: OFF
8021H Muting Forward Active 2 Muting forward sequence is still active. Both i_bMutingSw_21 and
i_bMutingSw_22 are actuated and the monitoring of
i_dDiscTime21_22 is stopped.
o_bReady: ON
o_bS_AOPD_Out: ON
o_bS_MutingActive: ON
o_bError: OFF
Complete muting within
i_dMaxMutingTime.
8122H Muting Backward Start 1 Muting backward sequence is in starting phase after rising trigger
of i_bMutingSw_21. Monitoring of i_dDiscTime21_22 is activated.
Monitoring of i_dMaxMutingTime is activated.
o_bReady: ON
o_bS_AOPD_Out: ON
o_bS_MutingActive: OFF
o_bError: OFF
Set both muting switches
(i_bMutingSw_21 and
i_bMutingSw_22) to ON.
Complete muting within
i_dMaxMutingTime.
8422H Muting Backward Start 2 Muting backward sequence is in starting phase after rising trigger
of i_bMutingSw_22. Monitoring of i_dDiscTime21_22 is activated.
Monitoring of i_dMaxMutingTime is activated.
o_bReady: ON
o_bS_AOPD_Out: ON
o_bS_MutingActive: OFF
o_bError: OFF
8121H Muting Backward Active 1 Muting backward sequence is active when both i_bMutingSw_21
and i_bMutingSw_22 have been actuated in the same cycle or in
serial. Monitoring of i_dDiscTime21_22 is stopped. Monitoring of
i_dMaxMutingTime is activated, when transition came directly from
state 8000H.
o_bReady: ON
o_bS_AOPD_Out: ON
o_bS_MutingActive: ON
o_bError: OFF
Complete muting within
i_dMaxMutingTime.
8114H Muting Backward Step 1 Muting backward sequence is active. i_bMutingSw_11 is the first
exit switch actuated. Monitoring of i_dDiscTime11_12 is started.
o_bReady: ON
o_bS_AOPD_Out: ON
o_bS_MutingActive: ON
o_bError: OFF
Set both muting switches
(i_bMutingSw_11 and
i_bMutingSw_12) to ON.
Complete muting within
i_dMaxMutingTime.
8414H Muting Backward Step 2 Muting backward sequence is active. i_bMutingSw_12 is the first
exit switch actuated. Monitoring of i_dDiscTime11_12 is started.
o_bReady: ON
o_bS_AOPD_Out: ON
o_bS_MutingActive: ON
o_bError: OFF
o_wDiagCode
(Hexadecimal)
State name Description, output setting Action