4 SAFETY FB SPECIFICATIONS
4.14 M+SF_TSSEN_R
95
4
Automatic test sequence
1. i_bStartTest=ON: o_bS_TestOut=OFF. Start monitoring time.
2. o_bS_TestOut signal stops the light of sensors. (Monitoring of i_dTestTime started for the first time)
3. i_bS_OSSD_In changes from ON to OFF. (Monitoring of i_dTestTime started for the second time)
4. o_bS_TestOut changes from OFF to ON.
5. Restart the light of sensors.
6. i_bS_OSSD_In changes from OFF to ON.
7. Stop monitoring time
8. o_bS_OSSD_Out is set to ON during testing.