8
2 DETAILS OF THE FB LIBRARY
2.1 M+ArrayHandling_PointAdd_R
Performance value
The following table lists the performance values of this FB under the following conditions.
CPU module: R04CPU
File register storage location: Extended SRAM cassette
FB compilation method: Subroutine type
*1 The time required from start to end of the processing
Restrictions and precautions (1) This FB does not include the error recovery processing. Prepare the error recovery processing separately to suit the
user's system and the expected operation.
(2) This FB uses the long index register LZ0. When using an interrupt program, do not use the corresponding index
register.
(3) The FB cannot be used in an interrupt program.
(4) Using the FB in a program that is to be executed only once, such as a subroutine program or a FOR-NEXT loop, has a
problem that i_bEN (execution command) can no longer be turned off and normal operation is not possible; Always use
the FB in a program that is capable of turning off the execution command.
(5) The FB requires the configuration of the ladder for every input label.
(6) This FB checks the input array data values before the operation execution to prevent an overflow or an underflow from
occurring during the operation. If a possibility of an overflow or an underflow is detected at this check, o_bErr (error
completion) turns on and 203H is stored in o_uErrId (error code). For the operation with the single-precision real
number, an error may occur depending on the combination of input array data values. Even after the input array data
values are checked, the instruction execution fault (operation error) may occur at the operation execution. If "RAS
Setting" of "CPU Parameter" is set to continue the processing even after an operation error occurs, o_bErr (error
completion) turns on and 203H is stored in o_uErrId (error code).
(7) If 3403H is stored in the special register SD0 (Latest self-diagnostic error code) of the CPU module due to an error
outside FB while i_bEN (execution command) of this FB is on, o_bErr (error completion) turns on and the processing of
the FB is interrupted. In addition, 204H is stored in o_uErrId (error code). However, if "RAS Setting" of "CPU
Parameter" is set to stop the processing after an operation error occurs, 204H is not stored in o_uErrId (error code).
Input label Time required for the
processing
*1
Maximum scan time Number of the scans
required for the
processing
Number of data points Data type selection
10000 points 0: Word [signed] 14ms 3.62ms 4 scans
1: Double Word [signed] 22.5ms 5.83ms
2: Single-precision real number 37.1ms 9.65ms
500000 points 0: Word [signed] 754ms 3.9ms 200 scans
1: Double Word [signed] 1210ms 6.16ms
2: Single-precision real number 1950ms 9.86ms
1000000 points 0: Word [signed] 1510ms 3.92ms 400 scans
1: Double Word [signed] 2400ms 6.17ms
2: Single-precision real number 3880ms 9.87ms