4 APPLICABLE FUNCTIONS
4.6 Drive recorder
307
4
Saving the drive recorder data in manual setting mode
Precautions
The storage area of the servo amplifier has a limit for the number of writings. When using the drive recorder with [Pr.
PF81.0] set to "2" (continuous sampling), consider the number of write times.
Record with desired data and triggers
1. Set [Pr. PF80.0 Drive recorder - Operation mode selection] to "1" (manual setting mode).
2. Set the sampling cycle, trigger condition, and other areas with servo parameters.
3. Set [Pr. PF81.0 Drive recorder - Sampling start selection] to "1" (start a single sampling) or "2" (continuous sampling
start). Sampling starts.
Reconfiguring parameters
Servo parameters that set the sampling cycle, trigger condition, and other areas cannot be changed during sampling. Use the
following procedure to change these parameters.
1. Set [Pr. PF81.0] to "0" (stop sampling) and stop sampling.
2. Set the sampling cycle, trigger condition, and other areas with servo parameters.
3. Set [Pr. PF81.0] to "1" or "2". Sampling starts.
Return to automatic setting mode
To save in the automatic setting mode, set [Pr. PF80.0] to "0" (automatic setting). The automatic setting mode operates
automatically.
Item Servo parameter Reference
Sampling cycle [Pr. PF80.2-3] Page 318 Servo parameter [B]
Trigger condition [Pr. PF82] to [Pr. PF86]
Channels for sampling [Pr. PF87] to [Pr. PF94]
Item Servo parameter Reference
Sampling cycle [Pr. PF80.2-3] Page 318 Servo parameter [B]
Trigger condition [Pr. PF82] to [Pr. PF86]
Channels for sampling [Pr. PF87] to [Pr. PF94]