<Handling precautions>
(1) Use a microSD memory card that complies with the SD standards. Check that
the microSD memory card has a logo on it of those shown to the right.
(2) SD memory cards to the SD standards include microSD and microSDHC mem-
ory cards. The capacities are available up to 32 GB.
(3) Insert the microSD memory card into the FTC control board in the direction
shown below.
(4) Before inserting or ejecting a microSD memory card, make sure to power o󰀨
the system. If a microSD memory card is inserted or ejected with the system
powered on, the stored data could be corrupted or the microSD memory card
be damaged.
*A microSD memory card is live for a short duration after the system is
powered o󰀨. Before insertion or ejection wait until the LED lamps on the FTC
control board are all o󰀨.
(5) The read and write operations have been veried using the following microSD
memory cards, however, these operations are not always guaranteed as the
specications of these microSD memory cards could change.
Manufacturer Model Tested in
Vantastek Vantastek 8GB microSDHC Sep. 2022
Longsys NC5MC2008G-52A39 Sep. 2022
Kingston SDCS2/32GBSP Sep. 2022
Before using a new microSD memory card (including the card that comes with
the unit), always check that the microSD memory card can be safely read and
written to by the FTC controller.
<How to check read and write operations>
a) Check for correct wiring of power supply to the system. For more
details, refer to section 4.1.
(Do not power on the system at this point.)
b) Insert a microSD memory card.
c) Power on the system.
d) The LED4 lamp lights if the read and write operations are successfully
completed. If the LED4 lamp continues blinking or does not light, the
microSD memory card cannot be read or written to by the FTC control-
ler.
(6) Make sure to follow the instruction and the requirement of the microSD
memory card’s manufacturer.
(7) Format the microSD memory card if determined unreadable in step (5). This
could make it readable.
Download an SD card formatter from the following site.
SD Association homepage: https://www.sdcard.org/home/
(8) FTC supports FAT12/FAT16/FAT32 le system but not NTFS/exFAT le
system.
(9) Mitsubishi Electric is not liable for any damages, in whole or in part, including
failure of writing to a microSD memory card, and corruption and loss of the
saved data, or the like. Back up saved data as necessary.
(10) Do not touch any electronic parts on the FTC control board when inserting or
ejecting a microSD memory card, or else the control board could fail.
Logos
Capacities
2 GB to 32 GB *2
SD speed classes
All
The microSD logo is a trademark of SD-3C, LLC.
*2 A 2GB microSD memory card stores up to 30 days of operation logs.
4. Electrical work
4.12 Using microSD memory card
FTC is equipped with a microSD memory card interface.
Using a microSD memory card can simplify main remote controller settings and can store operating logs. *1
*1 To edit main remote controller settings or to check operating data, an Ecodan service tool (for use with PC) is required
.
4.11 Forced cooling mode input (IN13)
● When IN13 is active, the mode (heating/cooling) is xed to cooling.
● SW7-2 changes the logic of IN13.
Name Terminal block
DIP SW7-2
OFF ON
IN13 TBI.4 3-4
Active at short
(Default setting)
Active at open
Notes:
Use non-voltage contact signals for the switch of IN13.
The mode (heating/cooling) does not switch under the condition such as
● within 60 minutes since the mode switched last time,
● during DHW mode or legionella prevention mode,
● during outdoor unit protection control,
● during emergency operation, oor dry up operation, or abnormality.
Check the mode with the main remote controller or the cooling signal output (OUT8 ON: cooling, OFF: heating).
Cooling
60 min
60 min
CoolingHeating
Active
Inactive
Heating/Cooling

Related product manuals