OCH683
SERVICE MANUAL
CONTENTS
1. REFERENCE MANUAL
...................................
2
2. SAFETY PRECAUTION
...................................
3
3. PARTS NAMES AND FUNCTIONS
.................
9
4. SPECIFICATIONS
...........................................
14
5. NOISE CRITERION CURVES
.........................
16
6. OUTLINES AND DIMENSIONS
......................
17
7. WIRING DIAGRAM
.........................................
18
8. REFRIGERANT SYSTEM DIAGRAM
............
19
9. TROUBLESHOOTING
....................................
20
10. SPECIAL FUNCTION
.....................................
35
11. DISASSEMBLY PROCEDURE
.......................
41
R32/R410A
INDOOR UNIT
Model name
indication for
MAIN UNIT
PARTS CATALOG (OCB683)
SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS
SPLIT-TYPE, AIR CONDITIONERS
Model name
indication for GRILLE
No. OCH683
December 2017
Notes:
• This manual describes ser-
vice data of the indoor units
only.
• RoHS compliant products
have <G> mark on the spec
name plate.
Indoor unit
[Model Name] [Service Ref.]
PLA-SM71EA
PLA-SM100EA
PLA-SM125EA
PLA-SM140EA
PLA-SM71EA.UK
PLA-SM100EA.UK
PLA-SM125EA.UK
PLA-SM140EA.UK
Grille model
[Model Name] [Service Ref.]
PLP-6EA
PLP-6EAL
PLP-6EAJ
PLP-6EALM
PLP-6EA PLP-6EAR1
PLP-6EAL PLP-6EALR1
PLP-6EAJ
PLP-6EALM

Questions and Answers

  • J
    Jose VazquezAug 12, 2025
    What to do if my Mitsubishi Electric PLA-SM71EA.UK displays 'PLEASE WAIT ? check code'?
    • T
      Tyler HamiltonAug 12, 2025
      If your Mitsubishi Electric Air Conditioner displays 'PLEASE WAIT ? check code', it could be due to the connector for the outdoor unit’s protection device not being properly connected. Ensure this connector is securely connected. Alternatively, it may be caused by reverse or open phase wiring for the outdoor unit’s power terminal block. In this case, you should check and rectify the phase wiring.
  • J
    Joshua FlynnAug 16, 2025
    What to do if the Mitsubishi Electric Air Conditioner trouble is reoccurring?
    • J
      John FreemanAug 16, 2025
      If the trouble with your Mitsubishi Electric Air Conditioner is reoccurring, determine the issue and take corrective measures as described in “9-3. SELF-DIAGNOSIS ACTION TABLE”. Additionally, perform troubleshooting steps to identify the cause of the problem, referring to “9-4. TROUBLESHOOTING OF PROBLEMS”.
  • S
    Shane CarneyAug 20, 2025
    What to do if Mitsubishi Electric Air Conditioner trouble is not reoccurring and is not logged?
    • A
      Angelica Johnson MDAug 20, 2025
      If the trouble with your Mitsubishi Electric Air Conditioner is not reoccurring and is not logged, re-check the abnormal symptom. Conduct troubleshooting to ascertain the cause of the trouble according to “9-4. TROUBLESHOOTING OF PROBLEMS”. If the cause is not ascertained, continue to operate the unit for the time being. It is possible that there is no abnormality concerning parts such as the electrical component, controller board, remote controller, etc.
  • M
    Michael WellsAug 25, 2025
    Why is the Mitsubishi Electric PLA-SM71EA.UK trouble not reoccurring but logged?
    • E
      Evelyn VangAug 25, 2025
      The Mitsubishi Electric Air Conditioner trouble might not be reoccurring but is logged due to temporary defects, such as the activation of protection devices in the refrigerant circuit including the compressor, poor wiring connections, or noise. Consider these temporary defects by re-checking the symptom and inspecting the installation environment, refrigerant amount, weather conditions when the trouble occurred, and wiring. After finishing the service, reset the check code logs and restart the unit. Also, it is possible that there is no abnormality in the electrical component, controller board, remote controller, etc.
  • L
    Lacey HarrisonAug 27, 2025
    Why does my Mitsubishi Electric PLA-SM71EA.UK log check codes for non-reoccurring issues?
    • J
      Joshua RussellAug 27, 2025
      If the trouble with your Mitsubishi Electric Air Conditioner is not reoccurring, but a check code has been logged, it might be due to temporary issues such as protection devices activating in the refrigerant circuit (including the compressor), poor wiring connections, or electrical noise. Here's what you should do: 1. Consider these temporary defects. Re-examine the symptoms, installation environment, refrigerant level, weather conditions when the issue occurred, and wiring. 2. After servicing, reset the check code logs and restart the unit. 3. Note that this could indicate that there is no abnormality in the electrical components, controller board, or remote controller.
  • M
    michellefreemanAug 31, 2025
    What to do if Mitsubishi Electric Air Conditioner trouble is not reoccurring and not logged check code?
    • G
      Gregory FlemingAug 31, 2025
      If the trouble with your Mitsubishi Electric Air Conditioner is not reoccurring and no check code has been logged, follow these steps: 1. Re-check the abnormal symptom. 2. If the cause isn't clear, continue operating the unit for a while. 3. Bear in mind that this situation may indicate no issues with parts such as the electrical components, controller board, or remote controller.
  • J
    John CollinsSep 4, 2025
    What to do if the trouble is not reoccurring and is logged in Mitsubishi Electric Air Conditioner?
    • M
      michellehernandezSep 4, 2025
      If the trouble with your Mitsubishi Electric Air Conditioner is not reoccurring but is logged, consider temporary defects such as the operation of protection devices in the refrigerant circuit including the compressor, poor wiring connections, or noise. Re-check the symptom, and check the installation environment, refrigerant amount, weather when the trouble occurred, and matters related to wiring. After service, reset check code logs and restart the unit. Note that there may be no abnormality in the electrical components, controller board, remote controller, etc.
  • C
    collinssherylSep 8, 2025
    What to do if the trouble is not reoccurring and is not logged in Mitsubishi Electric PLA-SM71EA.UK?
    • S
      Steve ShawSep 8, 2025
      If the trouble with your Mitsubishi Electric Air Conditioner is not reoccurring and is not logged, re-check the abnormal symptom. Conduct troubleshooting and ascertain the cause of the trouble. If the cause is not ascertained, continue to operate the unit for the time being. Note that there may be no abnormality concerning parts such as electrical components, controller board, remote controller, etc.

Mitsubishi Electric PLA-SM71EA.UK Specifications

General IconGeneral
BrandMitsubishi Electric
ModelPLA-SM71EA.UK
CategoryAir Conditioner
LanguageEnglish

Related product manuals