SERVICE MANUAL
INDOOR UNIT
PARTS CATALOG (OCB784)
SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS
SPLIT-TYPE, AIR CONDITIONERS
Model name
indication for
MAIN UNIT
Model name
indication for GRILLE
Indoor unit
[Model Name] [Service Ref.]
R32/R410A
No. OCH784
October 2021
CONTENTS
1. REFERENCE MANUAL ·······················2
2. SAFETY PRECAUTION ·······················2
3. PARTS NAMES AND FUNCTIONS ········8
4. SPECIFICATIONS ······························ 9
5. NOISE CRITERION CURVES ············· 11
6. OUTLINES AND DIMENSIONS ··········· 12
7. WIRING DIAGRAM ··························· 13
8. REFRIGERANT SYSTEM DIAGRAM ··· 14
9. TROUBLESHOOTING ······················· 15
10. FUNCTION SETTING ························ 30
11. SPECIAL FUNCTION ························ 31
12. DISASSEMBLY PROCEDURE ············ 35
13. REMOTE CONTROLLER ··················· 42
PLA-SM71EA2
PLA-SM100EA2
PLA-SM125EA2
PLA-SM140EA2
PLA-SM71EA2.UK
PLA-SM100EA2.UK
PLA-SM125EA2.UK
PLA-SM140EA2.UK
Grille model
[Model Name] [Service Ref.]
PLP-6EA
PLP-6EAL
PLP-6EAJ
PLP-6EALM2
PLP-6EA PLP-6EAR1
PLP-6EAL PLP-6EALR1
PLP-6EAJ
PLP-6EALM2

Questions and Answers

  • E
    Evelyn JohnsonAug 12, 2025
    What to do if my Mitsubishi Electric PLA-SM71EA2 Air Conditioner displays 'PLEASE WAIT ? check code'?
    • P
      prattedwardAug 12, 2025
      If your Mitsubishi Electric Air Conditioner displays 'PLEASE WAIT ? check code', it could be due to the connector for the outdoor unit’s protection device not being properly connected. Ensure this connector is securely connected. Alternatively, it may be caused by reverse or open phase wiring for the outdoor unit’s power terminal block. In this case, you should check and rectify the phase wiring.
  • J
    Jennifer HammondAug 16, 2025
    What to do if the Mitsubishi Electric PLA-SM71EA2 Air Conditioner trouble is reoccurring?
    • M
      Matthew MasseyAug 16, 2025
      If the trouble with your Mitsubishi Electric Air Conditioner is reoccurring, determine the issue and take corrective measures as described in “9-3. SELF-DIAGNOSIS ACTION TABLE”. Additionally, perform troubleshooting steps to identify the cause of the problem, referring to “9-4. TROUBLESHOOTING OF PROBLEMS”.
  • B
    Bridget JohnsonAug 19, 2025
    What to do if Mitsubishi Electric PLA-SM71EA2 Air Conditioner trouble is not reoccurring and is not logged?
    • C
      Cheryl VegaAug 19, 2025
      If the trouble with your Mitsubishi Electric Air Conditioner is not reoccurring and is not logged, re-check the abnormal symptom. Conduct troubleshooting to ascertain the cause of the trouble according to “9-4. TROUBLESHOOTING OF PROBLEMS”. If the cause is not ascertained, continue to operate the unit for the time being. It is possible that there is no abnormality concerning parts such as the electrical component, controller board, remote controller, etc.
  • B
    Bruce BurgessAug 23, 2025
    Why is the Mitsubishi Electric PLA-SM71EA2 Air Conditioner trouble not reoccurring but logged?
    • J
      James ShortAug 23, 2025
      The Mitsubishi Electric Air Conditioner trouble might not be reoccurring but is logged due to temporary defects, such as the activation of protection devices in the refrigerant circuit including the compressor, poor wiring connections, or noise. Consider these temporary defects by re-checking the symptom and inspecting the installation environment, refrigerant amount, weather conditions when the trouble occurred, and wiring. After finishing the service, reset the check code logs and restart the unit. Also, it is possible that there is no abnormality in the electrical component, controller board, remote controller, etc.
  • C
    Calvin BurnsAug 28, 2025
    Why does my Mitsubishi Electric Air Conditioner log check codes for non-reoccurring issues?
    • A
      April HoffmanAug 28, 2025
      If the trouble with your Mitsubishi Electric Air Conditioner is not reoccurring, but a check code has been logged, it might be due to temporary issues such as protection devices activating in the refrigerant circuit (including the compressor), poor wiring connections, or electrical noise. Here's what you should do: 1. Consider these temporary defects. Re-examine the symptoms, installation environment, refrigerant level, weather conditions when the issue occurred, and wiring. 2. After servicing, reset the check code logs and restart the unit. 3. Note that this could indicate that there is no abnormality in the electrical components, controller board, or remote controller.
  • D
    danasinghAug 31, 2025
    What to do if Mitsubishi Electric PLA-SM71EA2 trouble is not reoccurring and not logged check code?
    • W
      Wanda JohnsonAug 31, 2025
      If the trouble with your Mitsubishi Electric Air Conditioner is not reoccurring and no check code has been logged, follow these steps: 1. Re-check the abnormal symptom. 2. If the cause isn't clear, continue operating the unit for a while. 3. Bear in mind that this situation may indicate no issues with parts such as the electrical components, controller board, or remote controller.
  • K
    Kyle WheelerSep 3, 2025
    What to do if the trouble is not reoccurring and is logged in Mitsubishi Electric Air Conditioner?
    • K
      kaylamillerSep 3, 2025
      If the trouble with your Mitsubishi Electric Air Conditioner is not reoccurring but is logged, consider temporary defects such as the operation of protection devices in the refrigerant circuit including the compressor, poor wiring connections, or noise. Re-check the symptom, and check the installation environment, refrigerant amount, weather when the trouble occurred, and matters related to wiring. After service, reset check code logs and restart the unit. Note that there may be no abnormality in the electrical components, controller board, remote controller, etc.
  • K
    Kimberly BrownSep 7, 2025
    What to do if the trouble is not reoccurring and is not logged in Mitsubishi Electric Air Conditioner?
    • A
      arellanojamesSep 7, 2025
      If the trouble with your Mitsubishi Electric Air Conditioner is not reoccurring and is not logged, re-check the abnormal symptom. Conduct troubleshooting and ascertain the cause of the trouble. If the cause is not ascertained, continue to operate the unit for the time being. Note that there may be no abnormality concerning parts such as electrical components, controller board, remote controller, etc.

Mitsubishi Electric PLA-SM71EA2 Specifications

General IconGeneral
BrandMitsubishi Electric
ModelPLA-SM71EA2
CategoryAir Conditioner
LanguageEnglish

Related product manuals