Power source system error
(Power source to indoor control PCB)
1. Applicable model
5. Troubleshooting
All models
Diagnosis Countermeasure
Is
AC220/240V
detected between 1 and
2 on the terminal block
of indoor
unit?
NO
NO
Are fuses OK?
YES
YES
YES
NO
Is the
check of resistance
between - of CNW0
(FDU
: T1-T2)
OK?
Note(1) FDT, FDUM : F1, F2, FDU : F3
FDTC, FDF : F200, F201
FDEN : Fuse between wires.
NO
Is the
checked result
of resistance of fan
motor, etc
OK?
NO
NO
(2)
(1)
Note (2) for GND
Is DC5V
detected between -
of CNW1?
NO
Is
AC380/415V
for 3-phase unit
detected between 1, 2 and 3
on the teminal block
of outdoor unit?
YES
YES
YES
YES
Is JX1 open?
Defective outdoor control
PCB (Noise lter)
Misconnection or breakage
of connecting wires
Defective indoor power
PCB
Replace.
Replace fan motor, etc.
Replace fuse.
Defective indoor power
PCB
Replace.
Open JX1.
Defective indoor control
PCB
Replace.
2. Error detection method
3.
Condition of Error displayed
4. Presumable cause
Misconnection or breakage of
connecting wires
Blown fuse
Faulty transformer
Faulty indoor control or
power PCB
Broken harness
Faulty outdoor control PCB
(Noise filter)
Note:
Error code
Remote control:
LED Green Red
Indoor
Stays OFF Stays OFF
Outdoor
Stays OFF
2-time flash
Content
-
69
-
'14 • PAC-SM-215

Other manuals for Mitsubishi Heavy Industries FDC250VSA

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Mitsubishi Heavy Industries FDC250VSA and is the answer not in the manual?

Mitsubishi Heavy Industries FDC250VSA Specifications

General IconGeneral
BrandMitsubishi Heavy Industries
ModelFDC250VSA
CategoryAir Conditioner
LanguageEnglish

Related product manuals