(2) The operation data are applied to the 220V, 230V or 240V districts respectively.
(3) The refrigerant quantity to be charged includes the refrigerant in 7 m connecting piping.
(Purging is not required even in the short piping.)
If the piping length is longer, (When it is 7 to 15 m, add 20 g refrigerant per meter.)
(4) When the unit is operated in cooling or dehumidification mode at the outside air temperature of 1°C and less, there is a possibility that water leakage occurs
at the indoor unit.
Notes (1) The data are measured at the following conditions.
Model SRK56A, -4 (Indoor unit)
SRC56CA, -4 (Outdoor unit)
Item Indoor air temperature Outdoor air temperature
Standards
Operation DB WB DB WB
Cooling 27°C19°C35°C24°C ISO-T1, JIS C9612
Item
Model
SRK56A, -4 SRC56CA, -4
Cooling capacity
(1)
W 5000
Power source 1 Phase, 220/230/240V, 50 Hz
Cooling input kW 2.08
Running current (Cooling) A 9.7/9.3/8.9
Inrush current A 44/46/48
COP (In cooling) 2.40
Sound rating (Power level) dB 59 68
Exterior dimensions mm
298 × 798 × 203 640 × 850 × 290
Height × Width × Depth
Color Noble white Stucco white
Net weight kg 10 44
Refrigerant equipment
RM5526GNE4 (Rotary type) × 1
Compressor types & Q’ty
Motor kW 1.9
Starting method Line starting
Heat exchanger Louver fins & grooved tubing
Refrigerant control Capillary tubes
Refrigerant
(3)
kg R22 1.45
Refrigerant oil R 0.7 (BARREL FREEZE 32SAM)
Air handling equipment
Tangential fan × 1 Propeller fan × 1
Fan type & Q’ty
Motor W 23 35
Air flow (at High) CMM 11 39
Air filter, Q’ty Polypropylene net (washable) × 2–
Shock & vibration absorber Cushion rubber (for compressor)
Electric heater ––
Operation control
Wireless-Remote controller
Operation switch
Room temperature control MC. Thermostat
Pilot lamp RUN (Green), TIMER (Yellow),
ECONO (Orange), HI POWER (Green)
Safety equipment
Dome mounted protector (for compressor)
Internal thermostat (for fan motor)
O.D mm (in) Liquid line: φ6.35 (1/4") Gas line: φ12.7 (1/2")
Connecting method Flare connecting
Attached length of piping Liquid line: 0.5m
Gas line : 0.43m
Insulation Necessary (Both sides)
Drain hose Connectable
Power source cord 3m (3 cores with Earth)
Size × Core number 1.5mm
2
× 3 cores (Including earth cable)
Connecting method Terminal block (Screw fixing type)
Accessories (included) Mounting kit
Optional parts
Connection
wiring
Operation
data
(1)
Refrigerant
piping

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Mitsubishi Heavy Industries SRK56A and is the answer not in the manual?

Mitsubishi Heavy Industries SRK56A Specifications

General IconGeneral
BrandMitsubishi Heavy Industries
ModelSRK56A
CategoryAir Conditioner
LanguageEnglish

Related product manuals