5 - 75
MELSEC-A
5 DATA USED FOR POSITIONING CONTROL
Da.13
Parameter
Set the value as required for "
Da.12 Special start command".
Da.12
Special start command
Setting value Setting details
Block start (Normal start) Not used. (There is no need to set.)
Condition start
Wait start
Simultaneous start
1 to 10
Set the condition data No. (No. of
"condition data" set to perform
condition judgment)
(For details of the condition data, refer
to Section 5.5.)
Stop Not used. (There is no need to set.)
Repeated start (FOR loop) 0 to 255 Set the No. of repetitions.
Repeated start (FOR condition) 1 to 10
Set the condition data No. (No. of
"condition data" set to perform
condition judgment)
(For details of the condition data, refer
to Section 5.5.)