7 - 5
MELSEC-A
7 MEMORY CONFIGURATION AND DATA PROCESS
7.1.2 Buffer memory area configuration
The AD75 buffer memory is configured of the following types of areas.
Buffer memory address
Buffer memory area configuration
Axis 1 Axis 2 Axis 3
Writing
possibility
Basic parameter area 0 to 14 150 to 164 300 to 314
Detailed parameter area 15 to 66 165 to 216 315 to 366
Zero point return basic
parameter area
70 to 78 220 to 228 370 to 378
Parameter area
Zero point return detailed
parameter area
79 to 89 229 to 239 379 to 389
Possible
System monitor area 450 to 799
Monitor data area
Axis monitor area 800 to 899 900 to 999 1000 to 1099
Not possible
System control data area 1100 to 1149
Control data area
Axis control data area 1150 to 1199 1200 to 1249 1250 to 1299
Possible
Positioning data area
(No.1 to 100)
Positioning data area 1300 to 2299 2300 to 3299 3300 to 4299
4300 to 4349 4550 to 4599 4800 to 4849
Start block data area
4350 to 4399 4600 to 4649 4850 to 4899
Condition data area 4400 to 4499 4650 to 4749 4900 to 4999
Positioning start
information area
(No.7000)
Indirectly specification
data area
4500 to 4549 4750 to 4799 5000 to 5049
Possible
PLC CPU memo area
PLC CPU memo area 5050 to 5099
Possible
Block transmission area
Block transmission area 5100 to 6109
Possible
* Use of address Nos. skipped above is prohibited. If used, the system may not operate correctly.
(For details of the buffer memory address, refer to Appendix 12.)