EasyManua.ls Logo

Mitsubishi A1SD75P2-S3 - 9.2.8 Speed Control

Mitsubishi A1SD75P2-S3
622 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
9 - 46
MELSEC-A
9 MAIN POSITIONING CONTROL
9.2.8 Speed control
In "speed control"(" Da.2 Control method" = Forward run: speed control, Reverse
run: speed control), control is carried out in the axis direction in which the positioning
data has been set by continuously outputting pulses for the speed set in "
Da.7
Command speed" until the input of a stop command.
The two types of speed control are "Forward run: speed control" in which the control
starts in the forward run direction, and "Reverse run: speed control" in which control
starts in the reverse run direction.
Operation chart
The following chart shows the operation timing for speed control. The "in speed
control flag" (
Md.40 Status: b0) is turned ON during speed control.
t
V
BUSY signal
OFF
ON
Positioning start signal
OFF
ON
Positioning complete signal
OFF
Stop command
OFF
ON
Does not turn ON even
when control is stoppe
d
by stop command
OFF
ON
Md.40 Status:b0
In speed control flag
Da. 7 Command speed
[Y10,Y11,Y12]
[X4,X5,X6]
[X7,X8,X9]
Fig. 9.9 Speed control operation timing