14 - 29
MELSEC-
14 TROUBLESHOOTING
Relevant buffer memory address
Axis 1 Axis 2 Axis 3
Setting range
(Setting given in sequence program)
Remedy
74
75
224
225
374
375
(In standard mode)
1 to 1000000 [pulse/s]
1 to 600000000 [mm/min, etc.]
(In stepping motor mode)
1 to 62500 [pulse/s]
1 to 37500000 [mm/min, etc.]
76
77
226
227
376
377
(In standard mode)
1 to 1000000 [pulse/s]
1 to 600000000 [mm/min, etc.]
(In stepping motor mode)
1 to 62500 [pulse/s]
1 to 37500000 [mm/min, etc.]
78 228 378 0, 1
86 236 386 1 to 300
80
81
230
231
380
381
(In standard mode)
0 to 2147483647
(In stepping motor mode)
0 to 134217727
82 232 382 0, 1, 2 ,3
83 233 383 0, 1, 2 ,3
88 238 388 0, 1
Change the setting to within the setting range and turn
OFF then ON the PLC READY signal (Y1D).
Write the flash ROM again.
If the same error persists, replace the module.