116
-
Operation and setting from remote control
Operation and setting from remote control (continued)
<Note of “eco-Touch Remote Control”>
A : Refer to the instruction manual for RC-EX series C : Loading a utility software vie Internet
B : Refer to the installation manual for RC-EX series
<Availability of setting/operation on standard remote controls>
○:
Nearly same function setting and operations are possible. Blank column: Standard remote controls have not
this function.
△:
Similar function setting and opperations are possible.
Setting
display item Description
RC-EX
series
RC-E
series
1.Remote Control network
1 Control plural indoor units by a single remote control A remote control can control plural indoor units up to 16 (in one group of remote control network).
An address is set to each indoor unit.
2
Main/sub setting of remote controls A pair of remote controls (including optional wireless remote control) can be connected within the remote control
network. Set one to “Main” and the other to “Sub”.
B
2.TOP scrren, Switch manipulation
1 Menu "Control","State", or "Details" can be selected. (3-8) A
2 Operation mode "Cooling","Heating","Fan","Dry" or "Auto" can be set. A
3 Set temp. "Set temperature" can be set by 0.5˚C interval. A
4 Air flow direction "Air flow direction" [Individual flap control] can be set.
Select Enable or Disable for the “3D AUTO” (in case of FDK). *1
A
5 Fan speed "Fan speed" can be set. A
6 Timer setting "Timer operation" can be set. A
7 ON/OFF "On/Off operation of the system" can be done. A
8 F1 SW *1 The system operates and is controlled according to the function specified to the F1 switch. A
9 F2 SW *1 The system operates and is controlled according to the function specified to the F2 switch. A
10
Select the language *2 Select the language to display on the remote control.
Select from English, German, French, Spanish, Italian, Dutch, Turkish, Portuguese, Russian,Polish, Japanese and Chinese.
A
3.Useful functions
1
Individual flap control The moving range (the positions of upper limit and lower limit) of the flap for individual flap can be set.
Set also the left and right limit positions for FDK. *1
A
2
Anti draft setting *1
Details ..................You can set Enable or Disable for anti draft motion performed at each blow outlet in each operation mode.
ON/OFF setting .....You can set ON/OFF (operation/stop) of anti draft function for the enabled blow outlet set in Details. *2
A
When the panel with the anti-draft function is assembled.
3 Timer settings Set On timer by hour The period of time to start operation after stopping can be set.
The period of set time can be set within range of 1hour-12houres (1hr interval).
The operation mode, set temp and fan speed at starting operation can be set.
A
Set Off timer by hour The period of time to stop operation after starting can be set.
The period of set time can be set within range of 1hour-12houres (1hr interval).
A
Set On timer by clock The clock time to start operation can be set.
The set clock time can be set by 5 minutes interval.
[Once (one time only)] or [Everyday] operation can be switched.
The operation mode, set temp and fan speed at starting operation can be set.
A
Set Off timer by clock The clock time to stop operation can be set.
The set clock time can be set by 5 minutes interval.
[Once (one time only)] or [Everyday] operation can be switched.
A
Confirmation of timer settings Status of timer settings can be seen. A
4 Favorite setting
[Administrator password]
*1 Set the operation mode, setting temperature, air flow capacity and air flow direction for the choice setting operations.
Set them for the Favorite set 1 and the Favorite set 2 respectively.
A
5 Weekly timer On timer and Off timer on weekly basis can be set.
8-operation patterns per day can be set at a maximum.
The setting clock time can be set by 5 minutes interval.
Holiday setting is available.
The operation mode, set temp and fan speed at starting operation can be set.
A
6 Home leave mode
[Administrator password]
When leaving home for a long period like a vaction leave, the unit can be operated to maintain the room temperature not to be
hotter in summer or not to be colder in winter.
The judgment to switch the operation mode (Cooring
Heating) is done by the both factors of the set temp. and outdoor air temp.
The set temp. and fan speed can be set.
A
7 External Ventilation
When the ventilator is combined.
On/Off operation of the external ventilator can be done.
It is necessary to set from [Menu]
[Service setting]
[R/C function settings]
[Ventilation setting].
If the “Independent” is selected for the ventilation setting, the ventilator can be operated or stopped.
A
8 Select the language Select the language to display on the remote control.
Select from English, German, French, Spanish, Italian, Dutch, Turkish, Portuguese, Russian, Polish, Japanese and Chinese.*1
A
9
Silent mode control *2
The period of time to operate the unit by prioritizing the quietness can be set.
Start and end can be set for the silent mode
A
4.Energy-saving setting Administrator password
1 Sleep timer To prevent the timer from keeping ON, set hours to stop operation automatically with this timer.
The selectable range of setting time is from 30 to 240 minutes. (10 miuutes interval)
When setting is "Enable", this timer will activate whenever the ON timer is set.
A
2 Peak-cut timer Power consumption can be reduced by restructing the maximum capacity.
Set the [Start time], the [End time] and the capacity limit % (Peak-cut %
).
4-operation patterns per day can be set at maximum.
The setting time can be changed by 5-minutes interval.
The selectable range of capacity limit
(Peak-cut
) is from 0% to 40-80% (20
interval)
Holiday setting is available.
A
3 Automatic temp set back After the elapse of the set time period, the current set temp. will be set back to the [Set back time.]
The setting can be done in cooling and heating mode respectively.
Selectable range of the set time is from 20 min. to 120 min. (10 min. interval).
Set the [Set back temp.] by 1˚C interval.
A
4
Motion sensor control *1
When the motion sensor is used, it is necessary to set Enable or Disable for the “Power control” and the “Auto-off”.
A
When the panel with the motion sensor is assembled.
5.Filter
1
Filter sign reset
Filter sign reset The filter sign can be reset. A
Setting next cleaning date
The next cleaning date can be set. A
6.User setting
1
Internal settings
Clock setting The current date and time can be set or revised.
If a power failure continues no longer than 80 hours, the clock continues to tick by the built-in power source.
A
Date and time display [Display] or [Hide] the date and/or time can be set, and [12H] or [24H] display can be set. A
Summer time
When select [Enable], the +1hour adjustment of current time can be set. When select [Disable], the [Summer time] adjustment can be reset.
A
Contrast The contrast of LCD can be adjusted higher or lower. A
Backlight Switching on/off a light can be set and period of the lighting time can be set within the range of 5sec-90 sec (5sec interval). A
Controller sound It can set with or without [Controller sound (beep sound)] at touch panel. A
Operation lamp luminance *1 This is used to adjust the luminance of operation lamp. A
2
Administrator settings
[Administrator password]
Permission/Prohibition setting
Permission/Prohibition setting of operation can be set. [On/Off]
[Change set temp] [Change operation mode] [Change flap direction] [Change fan speed] [High power operation]
[Energy-saving operation] [Timer]
Request for administrator can be set.
[Individual flap control] [Weekly timer] [Select the language] [Anti draft setting *3]
*1
A
Outdoor unit silent mode timer The period of time to operate the outdoor unit by prioritizing the quiteness can be set.
The [Start time] and the [End time] for operating outdoor unit in silent mode can be set.
The period of the operation time can be set once aday by 5 minutes interal.
A
Setting temp range The upper/lower limit of temp. setting range can be set.
The limitation of indoor temp. setting range can be set for each operation mode in cooling and heating.
A
Setting
display item Description
RC-EX
series
RC-E
series
Temp increment setting
The temp increment setting can be changed by 0.5˚C or 1.0˚C. A
Set temp display Ways of displaying setting temperatures can be selected. A
2
Administrator settings
[Administrator password]
R/C display setting Register [Room name] [Name of I/U]
Display [Indoor temp display] or not.
Display [Error code display] or not.
Display [Heating stand-by display] [Defrost operation display] [Auto cooling/heating display] [Display temp of R/C, Room, Outdoor] or not
A
Change administrator password
The administrator password can be changed. (Default setting is "0000")
A
The administrator password can be reset.
B
F1/F2 function setting *1 Functions can be set for F1 and F2. Selectable functions: [Anti draft ON/OFF]
*2
[High power operation], [Energy-saving operation], [Silent mode cont.], [Home leave mode], [Favorite set 1],
[Favorite set 2] and [Filter sign reset].
A
7.Service setting
1 Installer settings
[Service password]
Installation date The [Installation date] can be registed.
When registering the [Instaration date], the [Next service date] is displayed automatically.
(For changing the [Next service date], please refer the item of [Service
Maintenance])
B
Company information The [Company information] can be registed and can be displayed on the R/C.
The [Company] can be registered within 26 characters.
The [Phone No.] can be registed within 13 digits.
B
Test run On/Off operation of the test run can be done.
B
Cooling test run The [Cooling test run] can be done at 5˚C of set temp. for 30 minutes.
Drain pump test run Only drain pump can be operated.
Staric pressure adjustment
In case of combination with only the ducted indoor unit which has a function of static pressure adjustment, the static pressure is adjustable.
It can be set for each indoor unit individually.
B
Change auto-address The set address of each indoor unit decided by auto-address setting method can be changed to any other address.
(For multiple KX units only)
B
Address setting of
main IU
Main indoor unit address can be set.
Only the Main indoor unit can change operation mode and the Sub indoor units dominated by the Main indoor shall follow.
The Main indoor unit can domain 10 indoor units at a maximum.
B
IU back-up function When a pair of indoor units (2 groups) is connected to one unit of remote control, it can be set Enable or Disable for the
[IU rotation], [IU capacity back-up] and [IU fault back-up]
B
Motion sensor setting *1
Set Enable or Disable for the infrared sensor detectors of indoor units connected to the remote control.
If Disable is selected, it cannot be control the motion sensor control for the energy-saving setting. B
When the panel with the motion
sensor is assembled.
2 R/C function setting
[Service password]
Main/Sub R/C The R/C setting of [Main/Sub] can be changed. B
Return air temp When two or more indoor units are connected to one unit of remote control, suction sensors, which are used for the
judgement by thermostat, can be selected.
It can be selected from [Individual], [Master IU] and [Average temp].
B
R/C sensor It can be set the mode to switch to the remote control sensor. It can be selected from cooling and heating. B
R/C sensor adjustment The offset value of [R/C sensor] sensing temp. can be set respectively in heating and cooling. B
Operation mode Enable or Disable can be set for each operation mode. B
ºC / ºF Set the unit for setting temperatures.
°C or °F can be selected.
B
Fan speed Fan speeds can be selected. B
External input When two or more indoor units are connected to one unit of remote control, the range to apply CNT inputs can be set. B
Upper/lower flap control [Stop at fixed position] or [Stop at any position] can be selected for the upper and lower louvers. B
Left/right flap control *1
[Fixed position stop] or [Stop at any position] can be selected for the right and left louvers. B
Ventilation setting Combination control for ventilator can be set. B
Auto-restart The operation control method after recovery of power failure happened during operation can be set. B
Auto temp setting [Enable] or [Disable] of [Auto temp setting] can be selected. B
Auto fan speed [Enable] or [Disable] of [Auto fan speed] can be selected. B
3
IU settings
Fan speed setting The fan speed for indoor units can be set. B
Filter sign The setting of filter sign display timer can be done from following patterns. B
[Service password] External input 1 The connect of control by external input 1 can be changed. B
External input 1 signal The type of external input 1 signal can be changed. B
External input 2 The connect of control by external input 2 can be changed. B
External input 2 signal The type of external input 2 signal can be changed. B
Heating thermo-OFF temp adjustment
The judgement temp. of heating themo-off can be adjusted within the range from 0 to +3˚C (1˚C interval) B
Return temperature adjustment The sensing temp. of return air temp. sensor built in the indoor unit can be adjusted within the range of ±2˚C. B
Fan control in cooling thermo-OFF Fan control, when the cooling thermostat is turned OFF, can be changed. B
Fan control in heating thermo-OFF Fan control, when the heating thermostat is turned OFF, can be changed. B
Anti-frost temp Judgment temperature for the anti-frost control during cooling can be changed. B
Anti-frost control When the anti-frost control of indoor unit in cooling is activated, the fan speed can be changed. B
Drain pump operation In any operation mode in addition to cooling and dry mode, the setting of drain pump operation can be done. B
Keep fan operating after cooling is stopped
The time period residual fan operation after stopping or thermo-off in cooling mode can be set. B
Keep fan operating after heating is stopped
The time period residual fan operation after stopping or thermo-off in heating mode can be set. B
Intermittent fan operation in heating
The fan operation rule following the residual fan operation after stopping or themo-off in heating mode can be set. B
Fan circulator operation In case that the fan is operated as the circulator, the fan control rule can be set. B
Control pressure adjust When only the OA processing units are operated, control pressure value can be changed. B
Auto operation mode The [Auto rule selection] for switching the operation mode automatically can be selected from 3 patterns. B
Thermo. rule setting When selecting [Outdoor air temp. control], the judgment temp can be offset by outdoor temp.. B
Auto fan speed control Auto switching range for the auto fan speed control can be set. B
IU overload alarm
If the difference between the setting temperature and the suction temperature becomes larger than the temperature difference set for
the overload alarm, at 30 minutes after the start of operation, the overload alarm signal is transmitted from the external output (CNT-5).
B
External output setting *1 Functions assigned to the external outputs 1 to 4 can be changed. B
4
Service & Maintenance
[Service password]
IU address
Max 16 indoor units can be connected to one remote control, and all address No. of the connected indoor units can be display ed.
The indoor unit conforming to the address No. can be identified by selecting the address No. and tapping [Check] to operate the
indoor fan.
B
Next service date The [Next service date] can be registered.
The [Next service date] and [Compa
ny information] is displayed on the message screen.
A B
Operation data The [Operation data] for indoor unit and outdoor unit can be displayed. B
Error display
B
Error history The error history can be displayed.
Display anomaly data The operation data just before the latest error stop can be displayed.
Erase anomaly data Anomaly operation data can be erased.
Reset periodical check The timer for the periodical check can be reset.
Saving IU settings
The I/U settings memorized in the indoor PCB connected to the remote control can be saved in the memory of the remote control.
B
Special settings [Erase IU address] [CPU reset] [Restore of default setting] [Touch panel calibration] B
Indoor unit capacity display *1 Address No. and capacities of indoor units connected to the remote control are displayed. B
8.Contact company Shows registered [Contact company] and [Contact phone].
9.Inspection
Confirmation of Inspection This is displayed when any error occurs. A
10.PC connection
USB connection Weekly timer setting and etc., can be set from PC. C
Listed items may not function depending on the specifications of indoor and outdoor units which are combined.
*1: Remote controls before RC-EX1A don't have this function. *2: Remote controls before RC-EX3 don't have this function. *3: RC-E series products don’t have this function.
*1: Remote controls before RC-EX1A don't have this function. *2: Remote controls before RC-EX3 don't have this function. *3: RC-E series products don’t have this function.