181
-
'20 • KX-T-373
-
133
-
'16 PAC-T-251
(37) Peak-cut timer (RC-EX3A only)
Power consumption can be reduced by restricting the maximum capacity.
Set the [Start time], the [End time] and the capacity limit % (Peak-cut %).
4-operation patterns per day can be set at maximum.
The setting time can be changed by 5-minutes interval.
The selectable range of capacity limit % (Peak-cut %) is from 0% to 40-80% (20% interval)
.
Holiday setting is available.
(33) Motion sensor control (RC-EX3A only)
The sensor determines the presence of people and the amount of activity, and the following controls are done by the motion
sensor. Following settings are necessary to activate motion sensor control.
(a) Infrared (motion) sensor setting : Installation setting of remote control.
The indoor unit which is set to "Enable" become valid.
(b) Infrared (motion) sensor control : Energy-saving setting of remote control.
The function which is set to "Enable" become valid.
(i) Power saving control
The set temperature is adjusted according to the presence of people and their amount of activity detected by the infrared
sensor.
(ii) Auto-off control
When no activity is deteced for 1 hour, unit will go stand-by mode. Unit will re-start operation automatically by activity
detection during the stand-by mode.
(38) Motion sensor control (RC-EX3A only)
The sensor determines the presence of people and the amount of activity, and the following controls are done by the motion sensor.
Following settings are necessary to activate motion sensor control.
(a) Infrared (motion) sensor setting: Installation setting of remote control
The indoor unit which is set to “Enable” become valid.
(b) Infrared (motion) sensor control: Energy-saving setting of remote control
The function which is set to “Enable” become valid.
(i) Power saving
/
comfort control
The set temperature is adjusted according to the presence of people and their amount of activity detected by the infrared (motion)
sensor.
(ii) Auto-off control
When no activity is detected for 1 hour, unit will go stand-by mode.
Unit will re-start operation automatically with the
original set temperature by activity detection during the stand-by mode. When stand-by mode continues for 12 hours,
unit stops.
Compressor keeps stopped regardless of the set temperature.
Notes (1) When the following operations are set, power saving control will be canceled.
Ener
gy-saving, Home leave mode, Warm-up control, Cooling operation check.
When the operation mode is changed DRY or FAN.
(2) Not operable while the air-conditioner is OFF.
Low
When the extent of human
activity is low
High
When the extent of human
activity is high
None
When there is no one in the
room
When the “None” continues for 1 hour, the
FAN SPEED is set Lo.
MODE:AUTO/COOL/HEAT mode operation
COOL
HEAT
Set
temperature
-3ºC
33ºC
15ºC
+3ºC
Heat Source & Activity Low
Normal
High None