Code
No.
Write content
Record data
Data write range
Unit of
write
Number of
bytes
Content
<Control status>
62 Control status
Oil return
0 - 2 1 0 None
1 Oil return ON
63 Control status
Defrost condition
0 - 3 1 0 None
1 Temperature condition
2 Time condition
64 Control status
Defrost status
0 - 4 1 0 None
1 Defrost status 1
2 Defrost status 2
3 Defrost status 3
4 Defrost status 4
65 Control status
Cooling low
pressure anomaly
recovering status
0 - 4 1 0 None
1 Status 1
2 Status 2
3 Status 3
4 Status 4
66 Control status 1 1 Bit0 Test run control implementing
0: Normal, 1: Implementing
Bit1 Demand control implementing
0: Normal, 1: Implementing
Bit2 Silent mode implementing
0: Normal, 1: Implementing
Bit3 (Spare)
Bit4
0: Normal, 1: Implementing
Bit5 (Spare)
Bit6
Fresh Air Intake Pre-treating
Unit Control
control at start/stop
Implementing pump down
0: Normal, 1: Implementing
Bit7
Low ambient air temperature
control implementing
0: Normal, 1: Implementing
67 Control status 2 1
Bit0
Pump-down control for
removal of unit implementing
0: Normal, 1: Implementing
Bit1 Compressor dilution protection
0: Normal, 1: Implementing
Bit2
(Spare)
Bit3
Forced out refrigerant from
indoor heat exchanger
0: Normal, 1: Implementing
Bit4 EEVKIT multi-setting status
0: Normal, 1: Implementing
Bit5 (Spare)
Bit6 (Spare)
Bit7 (Spare)
Code
No.
Write content
Record data
Data write range
Unit of
write
Number
of bytes
Content
<Protection control status>
68 Protection control
Status 1
1
Bit0
HP protection 1
Compressor capacity control
0: Normal, 1: Implementing
Bit1
HP protection 2
Indoor EEV minimal opening
control at heating stop
0: Normal, 1: Implementing
Bit2
HP protection 3
Indoor EEV Control at heating
overload
0: Normal, 1: Implementing
Bit3
HP protection 4
Indoor unit forced thermostat OFF
control under heating at overload
0: Normal, 1: Implementing
Bit4
LP protection 1
Compressor capacity control
0: Normal, 1: Implementing
Bit5
LP protection 2
Compressor speed increasing rate
control
0: Normal, 1: Implementing
Bit6
LP protection 3
Outdoor EEV control
0: Normal, 1: Implementing
Bit7
Td protection 1
Compressor capacity control
0: Normal, 1: Implementing
69 Protection control
Status 2
1
Bit0
Td protection 2
Compressor dilution ratio
protection control
0: Normal, 1: Implementing
Bit1
Td protection 3
Indoor EEV minimal opening
control at heating stop
0: Normal, 1: Implementing
Bit2
Td protection 4
Outdoor EEV control
0: Normal, 1: Implementing
Bit3
Compression ratio protection 1
Compressor capacity control
0: Normal, 1: Implementing
Bit4
Compression ratio protection 2
Outdoor EEV control
0: Normal, 1: Implementing
Bit5
CS protection 1
Compressor capacity control
0: Normal, 1: Implementing
Bit6
PT protection 1
Compressor capacity control
0: Normal, 1: Implementing
Bit7
(Spare)
70 Protection control
Status 3
1
Bit0
CS protection 2
Compressor frequency upper limit
control
0: Normal, 1: Implementing
Bit1 (Spare)
Bit2 (Spare)
Bit3 (Spare)
Bit4 (Spare)
Bit5 (Spare)
Bit6 (Spare)
Bit7 (Spare)
→*271
Cause of compressor stop
0 - 127 1
-
211
-
'20 • KX-T-373