[O/U 00]
[O/U 01 ]
[O/U 02 ]
⇔ ・・・
[O/U 31]
[I/U 001O/U 01] (1 sec.)
[ SET I/U ADD.] (1 sec.)
[I/U001 ] (Blink)
The switch will continuously change the display indication to the next one in every 0.25 seconds when it is pressed for 0.75 seconds or longer.
If the Reset switch is pressed during an operation, the display indication returns to the one that was shown before the last Set switch operation.
Even if an indoor unit No. is changed in this mode, the registered indoor unit No. before address change mode is displayed when [I/U SELECTION
] is shown.
When “SET COMPLETE” is shown, indoor unit No.’s are registered.
Set a new indoor unit No. with the switch.
A number indicated on the display will increase or decrease by 1 upon pressing the or switch
respectively.
Pressing the switch will change the display indication cyclically to show the unit
No.’s of the indoor units connected to the remote control and the unit No.’s of the
outdoor units connected with them.
Press the Set switch when the display shows “CHANGE ADD.
The lowest indoor unit No. among the indoor units connected to the remote control unit will be shown.
Set a new outdoor unit No. with the switch.
A number indicated on the display will increase or decrease by 1 upon pressing the or switch
respectively.
Set a new indoor unit No. with the switch.
A number indicated on the display will increase or decrease by 1 upon pressing the or switch
respectively.
Each time when you press the switch, the display indication will be switched.
(2) When plural indoor units are connected to the remote control.
When plural indoor units are connected, you can change their addresses without altering their cable connection.
Address change mode
Selecting an indoor unit
to be changed address
Setting a new indoor unit No.
1
2
3
Setting a new outdoor unit No.
Ending the session
4
5
Press the AIR CON Unit No. switch for 3 seconds or longer.
Each time when you press the switch, the display indication will be switched.
Then the address No. of the indoor unit to be changed is determined and the screen switches
to the display “ SET I/U ADD.”
After selecting an address, press the Set switch. Then the address No.of the indoor unit is determined.
The display will indicate the determined indoor address No. for 2 seconds and then switch to the
“ SET O/U ADD.” screen.
A default value shown on the display is the current address.
Set a new outdoor unit No. with the switch.
A number indicated on the display will increase or decrease by 1 upon pressing the or switch
respectively.
After selecting an address, press the Set switch.
Then the address of the indoor unit and outdoor unit are determined.
If you want to continue to change addresses, return to step
.
If you want to end the session (and reflect new address settings)
In Step
, press the switch to select “END .”
If you have finished changing addresses, press the Set switch while “END ” is shown. While new
settings are being transmitted, “SET COMPLETE” will be indicated. Then the remote control display
will change to the normal state.
If you want to end the session (without reflecting new address settings)
Before you complete the present address setting session, press the “ON/OFF” switch.
Then the display is change to exit from this mode and switch the display to the normal state.
All address settings changed in the session will be aborted and not reflected.
[I/U002](2 sec.)
[I/U 002](2 sec. lighting)
⇔[SET O/U ADD.](1 sec.)
⇔[O/U01 ](Blink)
[O/U00▲]
⇔[O/U01 ]
⇔[O/U02 ]
⇔ ・・・
⇔[O/U31▼]
[I/U 002O/U 02](2 sec. lighting)
→[SELECT](1 sec. lighting)
→[I/U SELECTION▼](lighting)
[Press the switch](1 sec.)
→[SET COMPLETE](210 sec.
lighting)
[END▲]
→[SET COMPLETE](210 sec. lighting)
Normal state
[ON/OFF]
Forced termination
[SELECT I/U](1 sec.)
→[I/U 001 O/U 01▲](Blink)
[CHANGE ADD▼]
⇔[MASTER I/U▲]
[CHANGE ADD▼]
[I/U 001 O/U 01▲」
⇔[I/U 002O/U 01  ]
⇔[I/U 003O/U 01  ]
⇔ ・・・
⇔[I/U 016 O/U 01▼」
[SET I/U ADD.](1 sec.)
→[I/U 001 ](Blink)
[I/U000▲]
⇔[I/U001 ]
⇔[I/U002 ]
⇔ ・・・
⇔[I/U127▼]
7-segment display indication in automatic address setting
Code Contents of a display
P30
P31
Items that are to be set by the customer
Turn on power to central control equipment after the addresses are determined.
Turning on power in wrong order may result in a failure to recognize addresses.
Communication protocol1: New SL mode
0: previos SL mode
Automatic address start
(The communication plotocol is displayed ; display only)
0: Automatic address standby
Item Operation Display
NOTICE
[I/U 000▲」
[I/U 001 ]
[I/U 002 ]
⇔ ・・・
[I/U 127]
[I/U 002] (2 sec. Lighting)
[ SET O/U ADD.] (1 sec.)
[O/U 01 ] (Blink)
Item
(1) When single indoor unit is connected to the remote control.
Address change mode
To set a new indoor unit No.
To set a new outdoor unit No.
1
2
3
Press the AIR CON No. switch for 3 seconds or longer.
Operation Display
Press the Set switch when the display shows “CHANGE ADD.
and then start the address change mode, changing the display indication to the “Indoor Unit No.
Setting” screen from the currently assigned address.
After selecting an address, press the Set switch, and then the indoor unit address No. is defined.
After showing the defined indoor address No. for 2 seconds, the display will change to the
“Outdoor Address No. Setting” screen.
The currently assigned address is shown as a default value.
After selecting an address, press the Set switch, and then the outdoor unit No. and the indoor
unit No. are defined.
[CHANGE ADD.]
[CHANGE ADD.]
[MASTER I/U]
[I/U 002 O/U 02] (2 sec. Lighting)
[SET COMPLETE] (2 sec. Lighting)
Returns to normal condition.
[I/U 002] (2 sec.)