271
-
'20 • KX-T-373
PCA012D025K
R
Precautions for Safety
Since the following precaution is the important contents for safety, be sure to observe them.
WARNING and CAUTION are described as follows:
WARNING Indicates an imminently hazardous situation which will result in death or serious
injury if proper safety procedures and instructions are not adhered to.
CAUTION Indicates a potentially hazardous situation which may result in minor or moderate
injury if proper safety procedures and instructions are not adhered to.
WARNING
Securely exchange the
PCB
according to this procedure.
If the PCB is incorrectly exchanged, it will cause an electric shock or fire.
Be sure to check that the power source for the outdoor unit is turned OFF before exchanging the PCB.
The PCB exchange under current-carrying will cause an electric shock or fire.
After finishing the PCB exchange, check that wiring is correctly connected with the PCB before
power distribution. If the PCB is incorrectly exchanged, it will cause an electric shock or fire.
CAUTION
Band the wiring so as not to tense because it will cause an electric shock.
Exchange the inverter PCB according to the following procedure.
1. Disassembly
1.1 After the breaker is shut down, remove the service panel and top panel. (Refer to Fig.1).
1.2 Don't touch the controller until three minutes have passed after the breaker is shut down.
(After having shut down the breaker, some capacitor is held by high voltage. It is very dangerous
to touch the controller in this condition.) Confirm the voltage (DC) is under 30 V with the harnesses
connected to control PCB. (Refer to Fig.2)
1.3 Unlock the band (1 place) and disconnect the connectors and round terminals from the user side of terminal block
and control PCB as shown in (A) in Fig.2.
1.4 Insert the CNP1 connector to the grommet of control panel. (Refer to Fig.2)
1.5 Cut the band as shown in (B) in Fig.2, and remove
the white wiring from CT1.
1.6 Cut the bands (4 places), while disconnect the CNLA connector and the faston terminals (Pand N2)
as shown in (C) in Fig.3.
1.7 Remove the screws of the electr
oly
tic capacitor as shown in Fig.3.
1.8 Remove the screws (8 places) as shown in Fig.4, and remove the control panel from nail-part in left-side
with pulling up. Next, disconnect CNI2 and CNI4, and remove the control panel from controller.
After elapsing 3 minutes
from power OFF
*Presence and shape of electric component
may vary according to model.
CNQ1
CNN1
CNR1
CNFAN1
CNEEV2
CNEEV1
CNL2
CNL1
CNP1
CNF2
CNTH
Insert the CNP1 connector to the grommet
(A)
Confirm the voltage (DC) is under 30 V
between No.1 and No.3 on CNA1
Fig.2 Parts arrangement view of controller and
voltage measurement points
Fig.3 Top view of controller
Fig.4 Removing procedure of control panel
1st. Remove the screws (8 places)
Control panel
CNI2
CNI4
Control panel
Inverter PCB
4th. Remove the control panel from controller
(B)
Control PCB
N.F. PCB
Band
White wiring
CT1
TB6
CNLA
Cut the band and remove
white wiring from CT1
2nd. Pull up the control panel and pull
towards oneself
3rd.
Disconnect the
connectors
Nail-part
Cut the bands (4 places)
Disconnect CNLA
A.F. module
Fig.1 Outdoor unit overall view
Remove
(Top panel)
Remove
(Service panel)
N2
P
(C)
Electrolytic capacitor (C1)
Remove the screws
Disconnect the faston terminals
CNP
1
CNF1
Terminal block (User side)
Unlock the band
Connectors are not
half inserted
(b) Invereter PCB
1) FDC121, 140, 155KXZEN1-W model