'17 • KX-T-264
To change setting
1. Remove the upper case of Control-Assy.
2. Change the setting by the switch on PCB.
3.
When SW1 is turned to OFF position, change the wireless remote control setting.
For the method of changing the setting, refer to Setting to avoid mixed communication of
④
Wireless remote control .
.
*The receivable area of the signal refer to
⑤
Receiver
.
Preparation before installation
Up to two receiver or wired remote
control can be installed in one
indoor unit group.
When two receiver or wired remote
control are used, it is necessary to
change SW on the PCB to set it as
slave.
How to install the receiver
Master/Slave setting when using
plural remote controls
1 2 3 4 5 6
ON
OFF
Terminal
Control Assy
upper case
Switch
Default settings
SW1
The Control-Assy and Display-Assy can be installed inside the indoor unit.
After turning off the power and safety, execute as follows.
①
Remove the front panel
(a) Remove the air inlet panel.
(b)
(c) Remove the 2 hooks of left and right side and then bottom panel can be removed. (Type 15 - 56 only)
(d)
(e)
Type 15 - 56 Type 71, 90
Air inlet panelFront panel
Front panel
Air inlet panel
Screw
Screw (in the cap)
Latch
Bottom panel
Screw (in the cap)
Screw
Latch
Setting on site
PCB on the receiver has the
following switches to set the function.
Default setting is shown with
mark.
SW1
Prevents interference
during plural setting
ON : Normal OFF : Customized
SW2
Receiver master/slave
setting
ON : Master OFF : Slave
SW3
Buzzer ON : Valid OFF : Invalid
SW4
Auto restart ON : Valid OFF : Invalid
SW5
Indication for error ON : Valid OFF : Invalid
SW6
Unit type ON : FDK OFF : FDTW, FDFW
Remove the screws (Type 15 - 56: 2 screws, Type 71, 90: 5 screws + 3 screws (in the cap))
Remove the upper latches and then front panel can be removed.
(Type 15 - 56: 4 latches, Type 71, 90: 5 latches)
Remove the 2 screws in the cap of bottom panel. (Type 15 - 56 only)
②
③
–
110
–